Loading...
HomeMy WebLinkAbout1999-O-03 - Uniform FIre CodeORDINANCE NO. 1999-3 An ordinance adopting the Uniform Fire Code prescribing regulations governing conditions hazardous to life and property from fire, hazardous materials or explosion; providing for the issuance of permits for hazardous uses or operations; and establishing a bureau of fire prevention and providing officers therefor and defining their powers and duties Be it ordained by the City of Stephenville, Texas. Sec. 1. ADOPTION OF UNIFORM FIRE CODE. There is hereby adopted by the city council of the City of Stephenville, Texas for the purpose of prescribing regulations governing conditions hazardous to life and property from fire, hazardous materials or explosion, that certain Code known as the Uniform Fire Code, including Appendix Chapters I-C, II-F, II-J, IV-B, V-A, VI-C and VI-E, published by the International Fire Code Institute, being particularly the 1997 edition thereof and the whole thereof, save and except such portions as are hereinafter deleted, modified or amended by Section 8 of this ordinance, one (1) copy of which has been and are now filed in the office of the city secretary and the same is hereby adopted and incorporated as fully as if set out at length herein, and from the date on which this ordinance shall take effect, the provision thereof shall be controlling within the limits of the City of Stephenville, Texas. Sec. 2. ESTABLISHMENT AND DUTIES OF BUREAU OF FIRE PREVENTION. 2.1 The Uniform Fire Code as adopted and amended herein shall be enforced by the bureau of fire prevention in the fire department of the City of Stephenville, Texas which is hereby established and which shall be operated under the supervision of the chief of the fire department. Sec.3. DEFINITIONS. 3.1 Wherever the word "jurisdiction" is used in the Uniform Fire Code, it is the City of Stephenville, Texas. 3.2 Wherever the words "chief of the bureau of fire prevention" are used they shall be held to mean "fire marshal'. Sec.4. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH STORAGE OF FLAMMABLE OR COMBUSTIBLE LIQUIDS IN OUTSIDE ABOVEGROUND TANKS IS PROHIBITED. The limits referred to in Sections 7902.2.2.1 and 7904.2.5.4.2 of the Uniform Fire Code in which the storage of flammable or combustible liquids is restricted are hereby established as follows: such tanks are prohibited within the city limits of Stephenville, except that such tanks may be located in Industrial zoning districts as established by the city council, provided that such tanks are located not less than one hundred (100) feet from: 1. Any residentially zoned property, 2. Any property having an assembly, educational or residential occupancy, or 3. Any other heavily congested commercial area. Sec.5. ESTABLISHMENT OF LIMITS IN WHICH STORAGE OF LIQUEFIED PETROLEUM GASES IS PROHIBITED. The limits referred to in Section 8204.2 of the Uniform Fire Code, in which storage of liquefied petroleum gas is restricted, are hereby established as follows: such tanks are prohibited within the city limits of Stephenville, except that such tanks may be located in Industrial zoning districts as established by the city council, provided that such tanks are located not less than one hundred (100) feet from: 1. Any residentially zoned property, 2. Any property having an assembly, educational or residential occupancy, or 3. Any other heavily congested commercial area. Sec.6. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH STORAGE OF EXPLOSIVES AND BLASTING AGENTS IS TO BE PROHIBITED. The limits referred to in Section 7701.7.2 of the Uniform Fire Code, in which storage of explosives and blasting agents is prohibited, are hereby established as follows: such explosives and blasting agents are prohibited within the city limits of Stephenville. Sec. 7. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH THE STORAGE OF COMPRESSED NATURAL GAS IS TO BE PROHIBITED. The limits referred to in Section 5204.5.2 of the Uniform Fire Code in which the storage of compressed natural gas storage is prohibited, are hereby established as follows: such storage is prohibited within the city limits of Stephenville, except that such storage may be located in Industrial zoning districts as established by the city council, provided that such tanks are located not less than one hundred (100) feet from: 1. Any residentially zoned property, 2. Any property having an assembly, educational or residential occupancy, or 3. Any other heavily congested commercial area. Sec. 8. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH THE STORAGE OF STATIONARY TANKS OF FLAMMABLE CRYOGENIC FLUIDS ARE TO BE PROHIBITED. The limits referred to in Section 3-1.5 of Uniform Fire Code Standard 80-3 in which the storage of flammable cryogenic fluids in stationary containers is prohibited are hereby established as follows: such storage is prohibited within the city limits of Stephenville, except that such storage may be located in Industrial zoning districts as established by the city council, provided that such tanks are located not less than one hundred (100) feet from: 2 i14 1. Any residentially zoned property, 2. Any property having an assembly, educational or residential occupancy, or 3. Any other heavily congested commercial area. See. 9. ESTABLISHMENT OF LIMITS OF DISTRICTS IN WHICH THE STORAGE OF HAZARDOUS MATERIALS IS TO BE PROHIBITED OR LIMITED. The limits referred to in Section 8001.1.1 of the Uniform Fire Code in which the storage of hazardous materials is prohibited or limited is hereby established as follows: such storage is prohibited in or on: 1. Any residentially zoned property, 2. Any property having an assembly, educational or residential occupancy, or 3. Any other heavily congested commercial area. Sec. 10. AMENDMENTS TO THE UNIFORM FIRE CODE. The Uniform Fire Code is amended and changed in the following respects {Underlined text underlined) indicates additions, text with over -striking (@;er stiking) indicates deletions]: [Section 214] change definition of "Mechanical Code to read as follows: MECHANICAL CODE is the International Mechanical CodeTm as adopted by this jurisdiction. ceo .l o ri, "' n& ,.i7,,,,i i [Section 220] add definition for "Self -Service Storage Facility: SELF-SERVICE STORAGE FACILITY is real property designed and used for the purpose of renting or leasing individual storage and removing personal property on a self-service basis. [Section 901.4.1] changed to read as follows: 901.4.1 General. Marking of fire apparatus access roads, address and fire protection equipment shall be in accordance with Section 901.4. See Section 902.2.3 for fire apparatus access road marking. [Section 901.4.4.1, 901.4.4.2 & 901.4.4.3] added to read as follows: 901.4.4.1 Complexes with multiple buildings. New and existing apartment complexes having more than one building shall be identified as follows: Building numbers and/or unit numbers shall be displayed in an approved manner on each building, so as to plainly identify each building. Where possible, the numbers shall be visible from the street fronting the property. Such numbers shall have a minimum height of four inches and a minimum stroke of one-half inch. The numbers and letters must be attached to a durable sign of contrasting color. The sign shall be attached to the building, and shall be a contrasting color. .35 When buildings are so located that the required identification cannot be made visible from the street as required above, such identification may be made visible from a central driveway within the complex. Where required by the chief, additional signs shall be installed to direct emergency traffic to those buildings. Other complexes, other than apartment complexes shall be similarly identified when deemed necessary by the chief. 901.4.4.2 Complexes with a single building. New and existing apartment complexes that are constructed in a single building shall have approved signs to direct emergency traffic where required by the chief. 901.4.4.3 Existing Numbering. Existing numbering may remain where approved by the chief. Examples to Section 901.4.4: 1205 W.CENTRAL BLDG 4 1205 W. CENTRAL UNITS 101-208 UNITS 101-208 UNITS 101-208 UNITS 115-221 IN BACK [Section 902.2.1] changed to read asfollows: Sec. 902.2.1 Required access. Fire apparatus access roads shall be provided in accordance with Sections 901 and 902.2 for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction when any portion of the facility or any portion of an exterior wall of the first story of the building is located more than 150 feet (45 720 mm) from fire apparatus access as measured by an approved route around the exterior of the building or facility. The path of measurement 136 shall be along a minimum of a ten (10) feet wide unobstructed pathway around the external walls of the structure. See also Section 902.3 for personnel access to buildings. 1 ... (balance to remain unchanged) [Section 902.2.2.1 ] changed to read as follows: 902.2.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm) and an unobstructed vertical clearance of not less than 13 Cost 6 inches in 1 1 c . An4 14 feet (4267 min . EXCEPTION: Vertical clearance may be reduced, provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved. Vertical clearances or widths shall be increased when, in the opinion of the chief, vertical clearances or widths are not adequate to provide fire apparatus access. [Section 902.2.3] changed to read as follows: Sec. 902.2.3 Marking. Either approved striping or signs shall be provided and maintained for fire apparatus access roads to identify such roads and prohibit the obstruction thereof or both. Strinine — Fire annaratus access roads shall be marked by painted lines of red traffic paint, six inches (6") in width to show boundaries of the lane. The words "NO PARKING FIRE LANE shall appear in four inch (4") white letters at 25 feet intervals on the red border markings along both sides of the fire lane. SIGNS -shall read "NO PARKING FIRE LANE" and shall be 12" wide and 18" hi¢h Signs shall be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (66") above finished grade. Signs shall be spaced not more than fifty feet (50') apart. Signs may be installed on permanent buildings or walls or as approved by the Fire Chief. [Section 903.4.2] changed to read as follows: Sec. 903.4.2 Required Installations. The location, number and type of fire hydrants connected to a water supply capable of delivering the required fire flow shall be provided on the public street or on the site of the premises or both to be protected as required and approved. Sao Appoi;dix II IL A fire hydrant shall be located within 100 feet of a fire department connection. 137 r Fire hydrants shall be spaced in accordance with the following: Occupancy Unsprinklered Sprinklered R-3 and U Occupancies 400' 600' All Others 300' 500' Hydrants shall be provided at all intersecting streets and at intermediate locations between intersections as prescribed above, measured as the hose would be laid. Fire hydrants shall be accessible to the fire department apparatus by roads meeting the requirements of Section 902.2. [Section 1003.1.2] changed to read as follows: 1003.1.2 Standards. n:.e avAi,. uishi% s 6tci;r, swan , ;a4ply *,ith thr Duildi% r ae Fire Protection systems shall comply with the appropriate Uniform Building Code Standards and National Fire Protection Association Standards. (See UBC Standard 9-1.) EXCEPTIONS: 1. Automatic fire -extinguishing systems not covered by the Building Code shall be approved and installed in accordance with approved standards. 2. Automatic sprinkler systems may be connected to the domestic water -supply main when approved by the building official, ... (balance of Exception #2 to remain unchanged) 3. Automatic sprinkler systems in Group R Occupancies four stories or less may be in accordance with the Building Code requirements for residential sprinkler systems. (See U.B.C. Standard 9-3.) 4. Automatic sprinkler systems in One- and Two -Family Dwellings and Manufactured Homes may be in accordance with U.B.C. Standard 9-7. Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards, however, every fire protection system shall be designed with a 5 psi margin of safety. [Section 1003.1.3] change to read as follows: 1003.1.3 Modifications. When residential sprinkler systems as set fourth in the Building Code (see UBC Standard 9-3) are provided, exceptions to, or reductions in, Building Code requirements based on the installation of an automatic fire -extinguishing system are not allowed. Allowable tradeoffs for, or increases in, Building Code provisions based on the installation of an automatic fire -extinguishing system are not allowed. EXCEPTION: Reductions are allowed for the following provisions: 1. Section 708.3.1.1.3 of the Building Code, draft stops in floor -ceiling assemblies. 2. Section 708.3.1.2.1 of the Building Code, draft stops in attics. 3. Section 708.3.1.2.2 of the Building Code, draft stops in attics. [Section 1003.2.2] item #5 is changed and item #6 is added to read as follows: 1003.2.2 All occupancies except Group R, Division 3 and Group U occupancies. 5. Throughout all buildings with a floor level, other than penthouses in compliance with Section 1511 of the Building Code, .,.:*w &q ^^^"^'^*'^"' Qf 39 ^- more that is located 55 feet (16 764 ram) or more above the lowest level of fire department vehicle access. EXCEPTIONS• ' Ai -poi" no;Awl tow"& 2. Open parking structures. 6. Spray Booths and Rooms. Spray booths and spraying rooms shall be protected by an approved automatic fire -extinguishing system. [Section 1003.2.6.4] added to read asfollows: 1003.2.6.4 Group H. Division 5 Occupancies. Aircraft hangers shall be classified by Group and Type*, and shall be provided with a fire -extinguishing system as specified by UBC Standard 9-4. (*Note: Any classification of construction type under UBC Standard 9-4 shall be for use with that standard only and shall have no bearing on the construction type used in conjunction with any other provision of this code.) [Section 1003.2.9] changed to read as follows: 1003.2.9 Group R, Division 1 Occupancies. An automatic sprinkler system shall be installed throughout every apartment house three or more stories in height or containing 16 or more dwelling units, every congregate residence three or more stories in height or having an occupant load of.1 a more than 10, and every hotel three or more stories in height or containing 20 or more guest rooms. Residential or quick -response standard sprinklers shall be used in the dwelling units and guest room portions of the building. [Sections 1003.2.10, 1003.2.10.1, 1003.2.10.21] added to read as follows: 1003.2.10.1 Self-service storage facilities. An automatic sprinkler system shall be installed throughout all self-service storage facilities. EXCEPTION: One-story self-service storage facilities, that have no interior corridors, with a one -hour fire -rated occupancy separation wall installed between every storage compartment. 1003.2.10.2 Group S, Division 5 Occupancies. Aircraft hangers shall be classified by Group and Type*, and shall be provided with a fire -extinguishing system as specified i by UBC Standard 9-4. (*Note: Any classification of construction type under UBC Standard 9-4 shall be for use with that standard only and shall have no bearing on the construction type used in conjunction with any other provision of this code.) n [Section 1003.4] subparagraph 4.4 of item #4 changed to read as follows: 1003.4 Permissible Sprinkler Omissions. 4.4 Other approved fire -protection equipment Class rr stall, pipo; 2x- is installed in such areas. [Section 1004.31 change the third paragraph to read as follows: 1004.3 Location of Class I Standpipe Hose Connections. There shall be a two-way outle at JoaRt on@ Q441st above the roof line on every standpipe when the roof has a slope of less than 4 units vertical in 12 units horizontal (33.3% slope). EXCEPTION: Where the stairway extends to the roof, the two-way outlet may be located at the topmost floor landing. [Section 1004.3] add a new paragraph to read as follows: 1004.3 Location of Class I Standpipe Hose Connections. <Add the following to the end of this section.> All class I standpipes shall be: 1. Water filled at all times, or 2. Supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low alarm. [Table 1004-A] change Occupancy Item 45, Standpipe Class for sprinklered buildings from "Alasequire+uan " to Class 'T'. Table 1004-A. - Standpipe Required Systems OCCUPANCY NONSPRINKLERED BUILDING SPRINKLERED BUILDINGS x304.8 for man x 0.0929 for m' Standpipe Class Hose Requirement Standpipe Class Hose Requirement 5. Groups l; H; B; S; M; F, Division I Occupancies less 4 stories in height but greater than II Yes Alarequirement I No 20,000 square feet per floor' [Section 1007.2.12.2.1] changed to read as follows: 1007.2.12.2.1 General. QrQup R ,.ffice buildings and Qreag A, blivisiea ' Occupancies, each having floors used for human occupancy located more than US 55 feet (22-96Q 16 764 mm) above the... (remainder of paragraph unchanged) ... with Section 1007.2.12.2. EXCEPTION: Open parking garages in compliance with Section 311.9 of the Building Code. [Section 1007.2.12.2.3] add a fourth paragraph to read as follows: 1007.2.12.2.3 Emergency voice alarm -signaling system. <add to end of section Actuation of anv automatic or manual device shall initiate an alarm signal on the alarming floor, the floor above, and the floor below and identify on an annunciator the zone or address from which the alarm signal originated. [Section 1007.2.12.2.4] change to read as follows: 1007.2.12.2.4 Fire department communication system. A two-way, approved fire department communication system shall be provided for fire department use. It shall operate between the central control station and elevators, elevator lobbies, emergency standby power rooms, fire pump room and inside stairways at each floor level. ! [Section 1007.2.12.6] changed to read as follows: ! 1 1007.2.12.6 Corridors in office uses. When required by the Building Code for corridors in lieu of one -hour corridor construction, smoke detectors shall be installed within office corridors in accordance with their listing. The actuation of any detector shall activate alarms audible in all areas served by the corridor. (See UBC Section 1004.3.4.3, Exception 4 and 6.) [Section 1007.3.1 ] add a second paragraph and exception to read as follows: 1007.3.1 Design Standards <add paragraph> All alarm systems new or replacement serving 50 or more alarm actuating devices shall be addressable fire detection systems. Alarm systems serving more than 75 smoke detectors or more than 200 total alarm activating devices shall be analog intelligent addressable fire detection systems EXCEPTION: Existing systems need not comply unless the total system remodel or expansion initiated after the adoption of this code exceeds 30% of the building. When cumulative building remodel or expansion exceeds 50% the building must comply within 18 months of permit application. [Section 1102.3] changed to read as follows: 1102.3 Open Burning. 41 1102.3.1 General. Open burning shall be conducted in accordance with Section 1102.3. Open burning shall also be conducted as required by other governing agencies regulating emissions. EXCEPTIONS: 1. Recreational fires shall be in accordance with Section 1102.4. 2. Bonfires shall be in accordance with Section 1102.6. 3. Open burning on remote, undeveloped property shall be in accordance with Section 1102.3.10. 1102.3.2 Notification. Prior to commencement of open burning, the fire department shall be notified. 1102.3.3 Material restrictions. p;o1aihi od Substances that may be burned include leaves, brush or other dry vegetation, and other approved materials, provided that it is piled or contained within an approved burning appliance. Unless otherwise approved, substances that may not be burned include construction and demolition waste, any asphaltic materials, garbage, paper or any other substance that may create a hazard or nuisance. Unless otherwise approved by the chief, the materials to be burned must have been generated at the site at which the burning is to take place. 1102.3.4 Time and atmospheric restrictions. Upo., bui4aing shall ,.. 3, ho p@;r -^,oa .,,hon tiRw and ...,.,diti..,s .,4..1yyith rho 1:,.4: 2 get 4f.4h i14 rho .. poll Burning must begin after 9:00 a.m. and must be completely extinguished before sundown. No burning shall take place when the wind is, or is predicted to be less than 5 mph, nor greater than 20 mph. No burning shall take place when atmospheric conditions are, or are predicted to be such that the smoke will not readily rise and dissipate. 1102.3.5 Location. Open burning shall not be conducted within 50 feet (15 240 mm) of any structure or other combustible material. Conditions that would cause the fire to spread to within 50 feet (15 240 mm) of a structure shall be eliminated prior to ignition. EXCEPTION: Clearance from structures and other combustibles is allowed to be reduced as follows: 1. Not less than 15 feet (4572 mm) when burning is conducted in an approved burning appliance. f 10 1'-12 2. Not less than 25 feet (7620mm) when the pile size is 3 feet (914 min) or less in diameter and 2 feet (610 mm) or less in height. 1102.3.6 Quantities. The maximum aggregate quantity that may be burned at any on site in residential, populated or other developed areas shall be three cubic yards. The maximum quantity that may be burned at any one time shall be one cubic yard. 1102.3.6 7 Fire -extinguishing equipment. A garden hose connected to a water supply or other approved fire -extinguishing equipment shall be readily available for use at open -burning sites. 1102.1-7 8 Attendance. Burning material shall be constantly attended by a person knowledgeable in the use of the fire -extinguishing equipment required by Section 1102 3 6 1102.3.7 and familiar with the permit limitations which restrict open burning. An attendant shall supervise the burning material until the fire has been extinguished. 1102.3.9 9 Discontinuance. The chief is authorized to require that open burning be immediately discontinued if the chief determines that smoke emissions are offensive to occupants of surrounding property or if the open burning is determined by the chief to constitute a hazardous condition. 1102.3.10 Open burning in remote, undeveloped areas. At the discretion of the chief, the foregoing regulations regarding the time of burning, location, quantities, and fire -extinguishing equipment may be modified. For the purposes of this section, remote, undeveloped areas shall include any property having sufficient size that the open burning can be conducted at least 300 feet from any adjacent properties which have residential, recreational, commercial or industrial use. [Section 1102.6] added to read as follows: 1102.6 Bonfires. 1102.6.1 General. Bonfires shall be conducted in accordance with Section 1102.6. 1102.6.2 Location. The location of bonfires in relation to structures, crowds and other items shall be subject to the approval of the chief. 1102.6.3 Fire -extinguishing equipment. The availability of fire extinguishing equipment at the site shall be as required by the chief. 1102.6.4 Attendance. The chief may require that the bonfire be constantly attended by a person who is knowledgeable of the use of the fire -extinguishing equipment required by Section 1102.6.3 and familiar with the limitations of the bonfire permit. An 11 143 attendant may be required to supervise the burning until the bonfire is completely extinguished. 1102.6.5 Discontinuance. The chief is authorized to require that a bonfire be immediately discontinued if the bonfire is determined by the chief to constitute a hazardous situation. [Section 1104] changed to read as follows: 1104 — PARADE FLOATS 1104.1 Decorative Material. Decorative material on parade floats shall be noncombustible or flame retardant. when: 1. the float is constructed on a motorized vehicle in which the operator of such vehicle is concealed, obstructed or in any way hindered from escaping the operator area, or 2. the float is constructed so that any occupants or passengers are restricted or hindered from escaping the float. 1104.2 Fire Protection. i.n^*^^zca ;adg floats ,^a *^^^^^ ;atus s'"" '— prgyidrd with 1_4In B-C _atod P014ablo f,..o r;aiA ' tom" readily All parade floats referred to in section 1104.1 shall be provided with at least one approved portable fire extinguisher, having a minimum rating of 2-A:10-B:C, located so that it is readily accessible to the occupants of the float. Floats that are constructed on a motorized vehicle in which the operator is concealed, obstructed or in any way hindered from escaping the operator area, shall be provided with an additional extinguisher, having a minimum rating of 2-A:10-B:C, located so that it is readily accessible to the operator. [Section 7801.3.1.1 ] changed to read as follows: 7801.3.1.1 Manufacturing. The manufacturing of fireworks is prohibited. LynOP4 coo gGG6014 Inc no.^,:. e.I. [Section 7802.3, Exception 1] delete exception 1, renumber exception 2 to exception 1: 7802.3 Prohibition. The storage, use and handling of fireworks are prohibited. EXCEPTION$: 1 Sto; g@ RAJ 1,aadl:.,g g fi;Q—@;kQ , allo cd , r-sd 2. 1. The use of fireworks for display is allowed as set forth in Section 7802.4. [Section 8102.8] change to read as follows: 8102.8.1 General. When curtain boards are required by Table 81-A, curtain boards shall be provided in accordance with Section 8102.8. Also see Footnote 2, Table 81 -B. 12 4 EXCEPTION: Fully sprinklered Group S occupancies, storing Class I -IV commodities, provided that a curtain board is installed between different system designs. [Sections 8203.2.1.9 & 8203-2.1.10] added to read as follows: 8203.2.1.9 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP -Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20- pound (9.6 kg) water capacity. Aggregate capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. 8203.2.1.10 Portable Gas Grills. LP -Gas containers are allowed to be used to supply portable grills at residential occupancies. Such containers shall not exceed 20-pound (9.0 kg) water capacity. [Section 8203.4] added to read as follows: 8203.4 Spas and Pool Heaters. Where natural gas service is not available, LP -Gas containers are allowed to be used to supply spa and pool heaters. Such containers shall not exceed 250-gallon water capacity. See Table 8204-A for location of containers. [Section 8204.2] exception added as follows: 8204.2 Maximum Capacity within Established Limits. Within the limits established by law restricting the storage of LP -gas for the protection of heavily populated or congested commercial areas, the aggregate capacity of any one installation shall not exceed a 2,000 -gallon (7571 L) water capacity (see sample adoption ordinance, Section 5). EXCEPTION: Except as permitted in 8203.4, LP -Gas containers are not allowed in residential areas. 13 ' 4 5 [Section 5.1 of Appendix II-F] changed to read as follows: 5.1 Restrictions. Protected above ground tanks shall not be located in any residential zoning district, nor in any B-1 Neighborhood Business District, as established by the city council. Any such tanks shall be located not closer than 25 feet from any residentially zoned property and at least 25 feet from any property having assembly, residential or educational use. <Renumber existing Section 5.1 to Section 5.2 and renumber remainder of Section 5 accordingly> [Appendix IV-B] changed to read as follows: Section 1 - SCOPE The use of natural or resin -bearing cut trees in all occupancies shall be in accordance with Appendix IV-B. EXCEPTION: Group R, Division 3 Occupancies and within individual dwelling units of Group R, Division 1 Occupancies. Section 3 2 — FLAME RETARDANCE Trees shall be properly treated with an approved flame retardant. Exception: The chief may waive this requirement when the tree is fresh (recently harvested) and all other provisions of Appendix IV-B are observed. Consideration should be also be given to humidity, temperature and the dryness of the tree at the time of setup. Section e Renumber remaining sections consecutively. [Appendix VI-E, TABLE 5-A] insert a footnote #8 to the heading "EXTERIOR WALLSB" and add the footnote to read asfollows: a When the exterior wall of a non -high-rise building is more than 20 feet from the property line, the fire -resistive requirements for exterior bearing and exterior nonbearing walls may be reduced by one -hour when the building is provided with an approved 14 146 automatic sprinkler system throughout as specified in Chapter 9. However, a wall that is required to be one -hour may not be reduced except as allowed under Section 508. S { [Appendix VI-E, Table 6-A] insert a footnote #4 in building element #8, "8. Roofs and roof -ceilings 1" and add a footnote #4 to read as follows: °The fire -resistive requirements for roofs of non -high-rise buildings may be reduced by one -hour when the building is provided with an approved automatic sprinkler system throughout as specified in Chapter 9. [Appendix VI-E, Table 8-B] change the rating for "Other Exitways "for Group R, Division 1 Occupancies from Cla" rr" to Class "1". Change footnote #2 to read as follows: 2Finish classification is not applicable to interior walls and ceilings of exterior exit balconies except as required in Section 310.13 of the Building Code for Group R, Division I Occupancies. Sec. 11. APPEALS. Whenever the chief disapproves an application or refuses to grant a permit applied for, or when it is claimed that the provisions of the code do not apply or that the true intent and meaning of the code have been misconstrued or wrongly interpreted, the applicant may appeal from the decision of the chief to the Board of Appeals according to Section 103.1.4 within 30 days from the date of the decision appealed. Sec. 12. NEW MATERIALS, PROCESSES OR OCCUPANCIES WHICH MAY REQUIRE PERMITS. The chief and the chief of the bureau of fire prevention shall act as a committee to determine and specify, after giving affected persons an opportunity to be heard, any new materials, processes or occupancies for which permits are required in addition to those now enumerated in the Uniform Fire Code. The chief of the bureau of fire prevention shall post such list in a conspicuous place at the bureau of fire prevention and distribute copies thereof to interested persons. Sec. 13. PENALTIES. 13.1 Any person who violates any of the provisions of the Uniform Fire Code as adopted and amended herein or fails to comply therewith, or who violates or fails to comply with any order made thereunder, or who builds in violation of any detailed statement of specifications or plans submitted and approved thereunder, or any certificate or permit issued thereunder, and from which no appeal has been taken, or who fails to comply with such an order as affirmed or modified by the Board of Appeals or by a 15 1 4 7 court of competent jurisdiction, within the required time, shall severally for each and every such violation and noncompliance, respectively, be guilty of a misdemeanor, punishable by a fine of not less than $50.00 nor more than $500.00. The imposition of one penalty for any violation shall not excuse the violation or permit it to continue; and all such persons shall be required to correct or remedy such violations or defects within a reasonable time; and when not otherwise specified, each ten days that prohibited conditions are maintained shall constitute a separate offense. 13.2 The application of the above penalty shall not be held to prevent the enforced removal of prohibited conditions. Sec. 14. REPEAL OF CONFLICTING ORDINANCES. All former ordinances or parts thereof conflicting or inconsistent with the provisions of this ordinance or of the Uniform Fire Code as adopted and amended herein are hereby repealed. Sec. 15. VALIDITY. The city council of the City of Stephenville, Texas hereby declares that should any section, paragraph, sentence or word of this ordinance or of the Uniform Fire Code as adopted and amended herein be declared for any reason to be invalid, it is the intent of the city council of the City of Stephenville, Texas that it would have passed all other portions of this ordinance independent of the elimination herefrom of any such portion as may be declared invalid. Sec. 16. DATE OF EFFECT. This ordinance shall be in full force and effect thirty (30) days from and after its final passage and adoption. PASSED AND APPROVED this 2n' day of March, 1999. City Administrator y Approved as to form and legality by Randy Thomas, City Attorney )hn Moser, Mayor 16 148