HomeMy WebLinkAbout2019-O-01 - Adoption of International Codes ORDINANCE NO. 2019-0-01
AN ORDINANCE OF STEPHENVILLE, TEXAS; ADOPTING THE 2015 EDITION OF THE INTERNATIONAL
BUILDING CODE; ADOPTING THE 2015 EDITION OF THE INTERNATIONAL MECHANICAL CODE;
ADOPTING THE 2015 EDITION OF THE INTERNATIONAL PLUMBING CODE; ADOPTING THE 2014
EDITION OF THE NATIONAL ELECTRICAL CODE; ADOPTING THE 2015 EDITION OF INTERNATIONAL
FUEL/GAS CODE; ADOPTING THE 2015 EDITION OF THE INTERNATIONAL RESIDENTIAL CODE;
ADOPTING THE 2015 EDITION OF THE INTERNATIONAL ENERGY CONSERVATION CODE;ADOPTING THE
2015 EDITION OF THE INTERNATIONAL EXISTING BUILDING CODE; ADOPTING THE 2015 PROPERTY
MAINTENANCE CODE; PROVIDING FOR THE COLLECTION OF PERMIT FEES; PROVIDING FOR
REGISTRATION AND LICENSE REQUIREMENTS FOR PLUMBING, MECHANICAL, AND ELECTRICAL
CONTRACTORS; PROVIDING FOR A PENALTY FOR VIOLATION HEREOF; PROVIDING THAT THIS
ORDINANCE IS CUMULATIVE OF ALL ORDINANCES; PROVIDING A SEVERABILITY CLAUSE; PROVIDING A
SAVINGS CLAUSE;AND ESTABLISHING THE EFFECTIVE DATE.
Section 150.01 Adoption of Building Code
The International Building Code, 2015 Edition, including Appendix, as published by the International
Code Council, a copy of which is on file in the office of the City Secretary, is hereby adopted, and
designated as the building code of the City of Stephenville, and is made a part hereof. In the event a
conflict is determined to exist between said International Building Code as adopted and the other
provisions of this code, the latter provisions shall be construed as controlling and taking precedence
over the former.
Section 150.02 Adoption of Mechanical Code
The International Mechanical Code, 2015 Edition, including Appendix, as published by the International
Code Council, a copy of which is on file in the office of the City Secretary, is hereby adopted, and
designated as the mechanical code of the City of Stephenville, and is made a part hereof. In the event a
conflict is determined to exist between said International Mechanical Code as adopted and the other
provisions of this code, the latter provisions shall be construed as controlling and taking precedence
over the former.
Section 150.03 Adoption of Plumbing Code
The International Plumbing Code, 2015 Edition, including Appendix, as published by the International
Code Council, a copy of which is on file in the office of the City Secretary, is hereby adopted, and
designated as the plumbing code of the City of Stephenville, and is made a part hereof. In the event a
conflict is determined to exist between said International Plumbing Code as adopted and the other
provisions of this code, the latter provisions shall be construed as controlling and taking precedence
over the former.
Section 150.04 Adoption of Electrical Code
The National Electrical Code, 2014 Edition, including Appendix, as published by the National Fire
Protection Association, a copy of which is on file in the office of the City Secretary, is hereby adopted,
and designated as the electrical code of the City of Stephenville, and is made a part hereof. In the event
a conflict is determined to exist between said National Electrical Code as adopted and the other
provisions of this code, the latter provisions shall be construed as controlling and taking precedence
over the former.
Section 150.05 Adoption of Fuel Gas Code
The International Fuel Gas Code, 2015 Edition, including Appendix, as published by the International
Code Council, a copy of which is on file in the office of the City Secretary, is hereby adopted, and
designated as the fuel gas code of the City of Stephenville, and is made a part hereof. In the event a
conflict is determined to exist between said International Fuel Gas Code as adopted and the other
provisions of this code, the latter provisions shall be construed as controlling and taking precedence
over the former.
Section 150.06 Adoption of Residential Code
The International Residential Code, 2015 Edition, including Appendix, as published by the International
Code Council, a copy of which is on file in the office of the City Secretary, is hereby adopted, and
designated as the residential code of the City of Stephenville, and is made a part hereof. In the event a
conflict is determined to exist between said International Residential Code as adopted and the other
provisions of this code, the latter provisions shall be construed as controlling and taking precedence
over the former.
Section 150.07 Adoption of Energy Conservation Code
The International Energy Conservation Code, 2015 Edition, including Appendix, as published by the
International Code Council, a copy of which is on file in the office of the City Secretary, is hereby
adopted, and designated as the energy conservation code of the City Of Stephenville, and is made a part
hereof. In the event a conflict is determined to exist between said International Energy Conservation
"" Code as adopted and the other provisions of this code, the latter provisions shall be construed as
controlling and taking precedence over the former.
Section 150.08 Adoption of Fire Code
The International Fire Code, 2015 Edition, including Appendix, as published by the International Code
Council, a copy of which is on file in the office of the City Secretary, is hereby adopted, and designated
as the building code of the City of Stephenville, and is made a part hereof. In the event a conflict is
determined to exist between said International Building Code as adopted and the other provisions of
this code, the latter provisions shall be construed as controlling and taking precedence over the former.
Section 150.09 Adoption of Existing Building Code
The International Existing Building Code, 2015 Edition, including Appendix, as published by the
International Code Council, a copy of which is on file in the office of the City Secretary, is hereby
adopted, and designated as the building code of the City of Stephenville, and is made a part hereof. In
the event a conflict is determined to exist between said International Building Code as adopted and the
other provisions of this code, the latter provisions shall be construed as controlling and taking
precedence over the former.
Section 150.10 Adoption of Property Maintenance Code
The International Building Code, 2015 Edition, including Appendix, as published by the International
Code Council, a copy of which is on file in the office of the City Secretary, is hereby adopted, and
designated as the building code of the City of Stephenville, and is made a part hereof. In the event a
conflict is determined to exist between said International Building Code as adopted and the other
'- provisions of this code, the latter provisions shall be construed as controlling and taking precedence
over the former.
Effective Date
This ordinance shall become effective immediately upon its passage.
PASSED AND APPROVED BY THE CITY COUNCIL OF THE CITY OF STEPHENVILLE, TEXAS, THIS 5TH DAY OF
FEBRUARY, 2019.
0011,1111,,,11,,,,,
pF S rep
(1\1‘
�` ' rr- Doug Svie ,-'Mayor
A-T riS rr * _
S
CO.
Azn a�
Kar Wilkerson, Deputy City Secretary
i• e. •y Al n L. Barnes
City Manager
`2,
Approved as to form and legality
Randy Thomas, City Attorney
Recommended Amendments to the
2015 International Fire Code
(#) North Central Texas Council of Governments Region
The following sections, paragraphs, and sentences of the 2015 International Fire Code (IFC) are hereby
amended as follows: Standard type is text from the IFC. Underlined type is text inserted. Lined-through
A double asterisk(") at the beginning of a section identifies an amendment
carried over from the 2012 edition of the code and a triple asterisk ("") identifies a new or revised
amendment with the 2015 code.
Note: Historically, the North Central Texas Council of Governments (NCTCOG) has limited Chapter 1
amendments in order to allow each city to insert their local policies and procedures. We now have
suggested certain items to be brought to the attention of cities considering adoption of the code that may
be of concern to several jurisdictions. It is still intended to be discretionary to each city to determine
which Chapter 1 amendments to include. Note that Appendices must be specifically adopted by
Ordinance. See Sample Ordinance on Page xii of 2015 IFC. Also, note that several sections of the code,
as indicated in the Sample Ordinance, require jurisdictional specificity as to dollar amounts, geographic
limits, etc.
Explanation of Options A and B:
Please note that as there is a wide range in fire fighting philosophies/capabilities of cities across the
region, OPTIONS"A" and "B" are provided in the Fire and Building Code amendments. Jurisdictions
should choose one of these based on their fire-fighting philosophies/capabilities when adopting code
amendments.
'Section 102.1;change#3 to read as follows:
3. Existing structures, facilities, and conditions when required in Chapter 11 or in specific sections of
this code.
(Reason: To clarify that there are other provisions in the fire code applicable to existing buildings that are
not located in Chas ter 11, such as Section 505 Premises Identification.
**Section 105.3.3;change to read as follows:
105.3.3 Occupancy Prohibited before Approval. The building or structure shall not be occupied prior to
the fire code official issuing a permit when required and conducting associated inspections indicating the
applicable provisions of this code have been met.
(Reason: For clarity to allow for better understanding in areas not requiring such permits, such as
uninco •orated areas of counties. This amendment ma be struck b a ci .
"*Section 105.7;add Section 105.7.19 to read as follows:
105.7.19 Electronic access control systems. Construction permits are required for the installation or
modification of an electronic access control system, as specified in Chapter 10. A separate construction
permit is required for the installation or modification of a fire alarm system that may be connected to the
access control system. Maintenance performed in accordance with this code is not considered a
modification and does not require a permit.
(Reason: Adds construction permit requirements for electronic access control systems affecting access
and/or egress to ensure proper design and installation of such systems. These changes reflect local
practices of municipalities in this region.)
North Central Texas Council of Governments 1 As of August 2015 IFC Amendments
**Section 202;amend and add definitions to read as follows:
** [B] AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical,
psychiatric, nursing, or similar care on a less than 24-hour basis to persons who are rendered incapable
of self-preservation by the services provided. This group may include but not be limited to the following:
- Dialysis centers
- Procedures involving sedation
-Sedation dentistry
-Surgery centers
-Colonic centers
-Psychiatric centers
(Reason:to clarify the range of uses included in the definition)
**[B] ATRIUM. An opening connecting twe three or more stories... (remaining text unchanged)
(Reason: Accepted practice in the region based on legacy codes. IBC Section 1009 permits unenclosed
two story stairways under certain circumstances.)
*** [B] DEFEND IN PLACE. A method of emergency response that engages building components and
trained staff to provide occupant safety during an emergency. Emergency response involves remaining in
place, relocating within the building, or both,without evacuating the building.
(Reason: Added from International Building Code (IBC) definitions for consistency in interpretation of the
subject requirements pertaining to such occupancies.)
**FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a
building or portion thereof by one or more qualified individuals or standby personnel when required by the
fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of
unwanted fire, raising an alarm of fire and notifying the fire department.
(Reason: Clearly defines options to the fire department for providing a fire watch.)
**FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for
entertainment purposes by combustion, deflagration, OF detonation, and/or activated by ignition with a
match or other heat producing device that meets the definition of 1.4G fireworks or 1.3G fireworks as set
forth herein. ... (remainder of text unchanged)...
(Reason: Increased safety from fireworks related injuries.)
**Option A
HIGH-PILED COMBUSTIBLE STORAGE:add a second paragraph to read as follows:
Any building classified as a group S Occupancy or Speculative Building exceeding 12,000 sq. ft. that
has a clear height in excess of 14 feet, making it possible to be used for storage in excess of 12 feet,
shall be considered to be high-piled storage. When a specific product cannot be identified, a fire
protection system and life safety features shall be installed as for Class IV commodities, to the
maximum pile height.
North Central Texas Council of Governments 2 As of August 2015 IFC Amendments
**Option B
HIGH-PILED COMBUSTIBLE STORAGE:add a second paragraph to read as follows:
Any building classified as a group S Occupancy or Speculative Building exceeding 6,000 sq. ft. that
has a clear height in excess of 14 feet, making it possible to be used for storage in excess of 12 feet,
shall be considered to be high-piled storage. When a specific product cannot be identified, a fire
protection system and life safety features shall be installed as for Class IV commodities, to the
maximum pile height.
(Reason: To provide protection for worst-case scenario in flexible or unknown situations.)
**Option A
HIGH-RISE BUILDING.(No Change Required)
**Option B
HIGH-RISE BUILDING. A building with an occupied floor located more than 75 55 feet (22 860 16 764
mm)above the lowest level of fire department vehicle access.
(Reason: Allows for additional construction safety features to be provided, based on firefighting
response capabilities.)
**REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor
vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of
motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks,
minor part replacement,and other such minor repairs.
(Reason: To further clarify types of service work allowed in a repair garage, as well as to correspond with
definition in the IBC.)
**SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or
leasing individual storage spaces to customers for the purpose of storing and removing personal property
on a self-service basis.
(Reason: To provide a definition that does not exist in the code.)
**STANDBY PERSONNEL. Qualified fire service personnel,approved by the Fire Chief. When utilized,
the number required shall be as directed by the Fire Chief. Charges for utilization shall be as normally
calculated by the jurisdiction.
***UPGRADED OR REPLACED FIRE ALARM SYSTEM. A fire alarm system that is upgraded or
replaced includes, but is not limited to the following:
• Replacing one single board or fire alarm control unit component with a newer model
• Installing a new fire alarm control unit in addition to or in place of an existing one
• Conversion from a horn system to an emergency voice/alarm communication system
• Conversion from a conventional system to one that utilizes addressable or analog devices
The following are not considered an upgrade or replacement:
• Firmware updates
• Software updates
• Replacing boards of the same model with chips utilizing the same or newer firmware
(Reason: This is referenced in several places, but the wording of"upgraded or replaced"is somewhat
ambiguous and open to interpretation. Defining it here allows for consistent application across the
region.)
North Central Texas Council of Governments 3 As of August 2015 IFC Amendments
**Section 307.1.1;change to read as follows:
307.1.1 Prohibited Open Burning. Open burning shall--be-prohibited that is offensive or objectionable
because of smoke emissions or when atmospheric conditions or local circumstances make such fires
hazardous shall be prohibited.
Exception: {No change.}
(Reason: To further protect adjacent property owners/occupants from open burning and/or smoke
emissions from open burning.)
**Section 307.2;change to read as follows:
307.2 Permit Required. A permit shall be obtained from the fire code official in accordance with Section
105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices,
prevention or control of disease or pests, or open burning-a--bonfire. Application for such approval shall
only be presented by and permits issued to the owner of the land upon which the fire is to be kindled.
Examples of state or local law, or regulations referenced elsewhere in this section may include but not be
limited to the following:
1. Texas Commission on Environmental Quality (TCEQ)guidelines and/or restrictions.
2. State, County, or Local temporary or permanent bans on open burning.
3. Local written policies as established by the fire code official.
(Reason: Amendments to 307.2, 307.4, 307.4.3, and 307.5 better explain current requirements and
recognize that jurisdictions have local established policies that best fit their environments.)
**Section 307.3;change to read as follows_
roI 307.3 Extinguishment Authority.
f The fire code official is authorized to order the
extinguishment by the permit holder, another person responsible or the fire department of open burning
that creates or adds to a hazardous or objectionable situation.
(Reason: Provides direction as to responsible parties relative to extinguishment of the subject open
burnin•.
**Section 307.4;change to read as follows:
307.4 Location. The location for open burning shall not be less than 50 300 feet (15 210 91 440 mm)
from any structure, and provisions shall be made to prevent the fire from spreading to within 50 300 feet
(15240 91 440 mm)of any structure.
Exceptions: {No change.}
(Reason: To increase the separation distance thereby increasing the safety to adjacent properties, as per
a p•licable TCEQ rules and re•ulations re•arding outdoor bumin•.)
**Section 307.4.3, Exceptions:add exception#2 to read as follows:
Exceptions:
2. Where buildings, balconies and decks are protected by an approved automatic sprinkler
system.
(Reason: To reflect similar allowances for open-flame cooking in these same locations.)
n North Central Texas Council of Governments 4 As of August 2015 IFC Amendments
**Section 307.4.4 and 5;add section 307.4.4 and 307.4.5 to read as follows:
307.4.4 Permanent Outdoor Firepit. Permanently installed outdoor firepits for recreational fire purposes
shall not be installed within 10 feet of a structure or combustible material.
Exception: Permanently installed outdoor fireplaces constructed in accordance with the
International Building Code.
307.4.5 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with
Section 307.2.
(Reason: To provide a greater level of safety for this potentially hazardous fire exposure condition.
Decrease in separation distance allowed for outdoor firepits due to permanent nature of construction
havin• substantial securement.)
**Section 307.5;change to read as follows:
307.5 Attendance. Open burning, trench burns, bonfires, recreational fires, and use of portable outdoor
fireplaces shall be constantly attended until the... (Remainder of section unchanged)
Reason: Adds attendance for trench burns based on •revious amendment •rovision for such.
"Section 308.1.4;change to read as follows:
308.1.4 Open-flame Cooking Devices. Open-flame cooking devices,
charcoal grills and other similar devices used for cooking shall not be operated-located or used on
combustible balconies, decks, or within 10 feet(3048 mm)of combustible construction.
Exceptions:
1. One-and two-family dwellings, except that LP-gas containers are limited to a water capacity not
greater than 50 pounds (22.68 kg) (nominal 20 pound (9.08 kg) LP-gas capacity] with an
aggregate LP-gas capacity not to exceed 100 lbs(5 containers).
2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system,
except that LP-gas containers are limited to a water capacity not greater than 50 pounds (22.68
kg) (nominal 20 pound (9.08 kg) LP-gas capacity), with an aggregate LP-gas capacity not to
exceed 40 lbs(2 containers).
3. {No change.}
(Reason: Decrease fire risk in multi-family dwellings and minimizes ignition sources and clarify allowable
limits for 1 & 2 family dwellings, and allow an expansion for sprinklered multi-family uses. This
amendment adds clarification and defines the container size allowed for residences.)
"*Section 308.1.6.2,Exception#3;change to read as follows:
Exceptions:
3. Torches or flame-producing devices in accordance with Section 308.4 308.1.3.
(Reason: Section identified in •ublished code is inappropriate.)
***Section 308.1.6.3;change to read as follows:
308.1.6.3 Sky Lanterns. A person shall not release or cause to be released and unmanned
free-floating devices containing an open flame or other heat source, such as but not limited to a sky
�1 lantern.
/' '1 North Central Texas Council of Governments 5 As of August 2015 IFC Amendments
(Reason: Eliminates the potential fire hazard presented by utilization of such devices and the potential
accidental release of such devices.)
**Section 311.5;change to read as follows:
311.5 Placards. Any The fire code official is authorized to require marking of any vacant or abandoned
buildings or structures determined to be unsafe pursuant to Section 110 of this code relating to structural
or interior hazards, as required by Section 311.5.1 through 311.5.5.
(Reason: There may be situations where placarding is not desired or necessary; also clarifies intent that
it is not the fire code official's responsibility to provide the placard.)
***{Note that prior amendment to Section 401.9 in the 2012 IFC recommended amendments has been
relocated to Section 901.6.3 as a more appropriate location for the requirement.)
***Section 403.5;change Section 403.5 to read as follows:
403.5 Group E Occupancies. An approved fire safety and evacuation plan in accordance with Section
404 shall be prepared and maintained for Group E occupancies and for buildings containing both a Group
E occupancy and an atrium. A diagram depicting two evacuation routes shall be posted in a conspicuous
location in each classroom. Group E occupancies shall also comply with Sections 403.5.1 through
403.5.3.
(Reason: The diagrams are intended to assist with egress in such occupancies—specifically, the primary
teacher is not always present to assist children with egress. Also, such will help reinforce evacuation drill
requirements.)
***Section 404.2.2;add Number 4.10 to read as follows:
4.10 Fire extinguishing system controls.
(Reason: The committee believed this information could be of great help to such plans to facilitate
locatin• sprinkler valves to minimize water dama•e, for instance.)
***Section 405.4;change Section 405.4 to read as follows:
405.4 Time. The fire code official may require an evacuation drill at any time. Drills shall be held at
unexpected times and under varying conditions to simulate the unusual conditions that occur in case of
fire.
(Reason: This chan.e clarifies who may require a fire or evacuation drill).
**Section 501.4;change to read as follows:
501.4 Timing of Installation. When fire apparatus access roads or a water supply for fire protection is
required to be installed for any structure or development, they shall be installed, tested, and approved
prior to the time of which construction has progressed beyond completion of the foundation of any
structure. ,
(Reason: Reflects current practice in the region relative to ensuring fire department and EMS access
during construction, which can be a time of increased frequency for emergency incidents.)
eTh North Central Texas Council of Governments 6 As of August 2015 IFC Amendments
**Section 503.1.1;add sentence to read as follows:
leN Except for one-or two-family dwellings, the path of measurement shall be along a minimum of a ten feet
(10')wide unobstructed pathway around the external walls of the structure.
(Reason: Recognizes that the hose lay provision can only be measured along a pathway that is wide
enough for fire fighter access.)
**Section 503.2.1;change to read as follows:
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 28
24 feet (6096-ram 7315 mm), exclusive of shoulders, except for approved security gates in accordance
with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (1115 mm)
14 feet(4267 mm).
Exception: Vertical clearance may be reduced: provided such reduction does not impair access by
fire apparatus and approved signs are installed and maintained indicating the established vertical
clearance when approved.
(Reason: Amendments to 503.2.1 and 503.2.2 recognize that the equipment now used in firefighting is
increasing in size. The code already recognizes that larger dimensions may be required under Section
503.2.2. The amendments are to standardize the dimensions for this area. With the increase in fire
a••aratus size, this will allow for the passa•e of two fire apparatus durin• a fire or EMS emergency.)
**Section 503.2.2;change to read as follows:
503.2.2 Authority. The fire code official shall have the authority to require an increase in the minimum
access widths and vertical clearances where they are inadequate for fire or rescue operations.
(Reason: Amendments to 503.2.1 and 503.2.2 recognize that the equipment now used in firefighting is
1.4.11 increasing in size. The code already recognizes that larger dimensions may be required under Section
503.2.2. The amendments are to standardize the dimensions for this area. With the increase in fire
apparatus size, this will allow for the passage of two fire ap•aratus during a fire or EMS emergency.)
***Section 503.2.3;change Section 503.2.3 to read as follows:
503.2.3 Surface. Fire apparatus access roads shall be designed and maintained to support imposed
loads of 80,000 Lbs for fire apparatus and shall be surfaced so as to provide all-weather driving
capabilities.
(Reason: To address the current size of fire trucks in use — figure derived from DOT requirements for
waiver of vehicle exceeding such weight.)
**Section 503.3;change to read as follows:
503.3 Marking.
markings that include the words NO PARKING — FIRE I ANE Striping, signs, or other markings, when
approved by the fire code official, shall be provided for fire apparatus access roads to identify such roads
or prohibit the obstruction thereof. Striping, signs and
other markings shall be maintained in a clean and legible condition at all times and be replaced or
repaired when necessary to provide adequate visibility.
(1)Striping—Fire apparatus access roads shall be continuously marked by painted lines of red traffic
paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING FIRE
LANE"or"FIRE LANE NO PARKING"shall appear in four inch (4")white letters at 25 feet intervals on
the red border markings along both sides of the fire lanes. Where a curb is available, the striping
r 1 North Central Texas Council of Governments 7 As of August 2015 IFC Amendments
shall be on the vertical face of the curb.
(2) Signs—Signs shall read "NO PARKING FIRE LANE"or"FIRE LANE NO PARKING"and shall be
(44, 12"wide and 18" high. Signs shall be painted on a white background with letters and borders in red,
using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the
bottom of the skin shall be six feet, six inches (6'6")above finished grade. Signs shall be spaced not
more than fifty feet (50') apart along both sides of the fire lane. Signs may be installed on permanent
buildings or walls or as approved by the Fire Chief.
(Reason: Establishes a standard method of marking and reflects local long-standing practices.)
**Section 503.4;change to read as follows:
503.4 Obstruction of Fire Apparatus Access Roads. Fire apparatus access roads shall not be
obstructed in any manner, including the parking of vehicles. The minimum widths and clearances
established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be
maintained at all times.
(Reason: As originally worded, the section implied that vehicles could be parked in the marked fire lane
and not be in violation if the minimum width is still maintained. Current accepted enforcement practice is
to require the entire marked fire lane to be maintained clear and unobstructed.)
**Section 505.1;change to read as follows:
505.1 Address Identification. New and existing buildings shall be provided with approved address
identification. The address identification shall be legible and placed in a position that is visible from the
street or road fronting the property. Address identification characters shall contrast with their background.
Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out.
Each character shall be not less than 4-inches-(40 6 inches(152.4 mm) high with a minimum stroke
1rs
width of 1/2 inch (12.7 mm). Where required by the fire code official, address numbers shall be provided
in additional approved locations to facilitate emergency response. Where access is by means of a private
road. buildings do not immediately front a street. and/or the building cannot be viewed from the public
way, a monument, pole or other sign with approved 6 inch (152.4 mm) height building numerals or
addresses and 4 inch (101.6 mm) height suite/apartment numerals of a color contrasting with the
background of the building or other approved means shall be used to identify the structure. Numerals or
addresses shall be posted on a minimum 20 inch (508 mm) by 30 inch (762 mm) background on border.
Address identification shall be maintained.
Exception: R-3 Single Family occupancies shall have approved numerals of a minimum 3 '/
inches (88.9 mm) in height and a color contrasting with the background clearly visible and legible
from the street fronting the property and rear alleyway where such alleyway exists.
(Reason: To increase the minimum addressing requirements for commercial properties and establish a
minimum for single-family residential properties Such improves legibility of these signs which are critical
to emergency response in a more timely manner.)
**Section 507.4;change to read as follows:
507.4 Water Supply Test Date and Information. The water supply test used for hydraulic calculation of
fire protection systems shall be conducted in accordance with NFPA 291 "Recommended Practice for Fire
Flow Testing and Marking of Hydrants" and within one year of sprinkler plan submittal. The fire code
official shall be notified prior to the water supply test. Water supply tests shall be witnessed by the fire
code official, as required
The exact location of the static/residual hydrant and the
flow hydrant shall be indicated on the design drawings. All fire protection plan submittals shall be
accompanied by a hard copy of the waterflow test report, or as approved by the fire code official. The
( North Central Texas Council of Governments 8 As of August 2015 IFC Amendments
report must indicate the dominant water tank level at the time of the test and the maximum and minimum
operating levels of the tank, as well, or identify applicable water supply fluctuation. The licensed
contractor must then design the fire protection system based on this fluctuation information, as per the
roll applicable referenced NFPA standard. Reference Section 903.3.5 for additional design requirements.
(Reason: Clarifies intent of the test to ensure contractor accounts for water supply fluctuations.)
**Section 507.5.4;change to read as follows:
507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. Posts,
fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire
hydrants,fire department inlet connections or fire protection system control valves in a manner that would
prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not
be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants.
(Reason: Maintains wording from 2006 Code to ensure these critical devices are available in an
emergency incident.)
**Section 509.1.2;add new Section 509.1.2 to read as follows:
509.1.2 Sign Requirements. Unless more stringent requirements apply, lettering for signs required by
this section shall have a minimum height of 2 inches (50.8 mm) when located inside a building and
4 inches(101.6 mm)when located outside, or as approved by the fire code official. The letters shall be of
a color that contrasts with the background.
(Reason:Provides direction as to appropriate si•n criteria to develop consistency in this re.and.)
**Section 603.3.2.1, Exception;change exception to read as follows:
Exception: The aggregate capacity limit shall be permitted to be increased to 3,000 gallons(11,356 L) in
accordance with all requirements of Chapter 57.
rgreuad-tanks... {Delete remainder of Exception)
(Reason: Change to Section 5704.2.9.5 is included in this amendment package.)
**Section 603.3.2.2;change to read as follows:
603.3.2.2 Restricted Use and Connection. Tanks installed in accordance with Section 603.3.2 shall be
used only to supply fuel oil to fuel-burning or generator equipment installed in accordance with Section
603.3.2.4. Connections between tanks and equipment supplied by such tanks shall be made using
closed piping systems.
(Reason: Relocate the exception to Chapter 57 for applicability to generator sets, due to contradictory
charging statement in 603.1 to not apply to internal combustion engines. Further, such large quantities of
combustible liquid are more thoroughl addressed in Chapter 57 relative to such tanks.)
***Section 604;change and add to read as follows:
604.1.1 Stationary Generators. Stationary emergency and standby power generators required by this
code shall be listed in accordance with UL 2200.
604.1.2 Installation. Emergency power systems and standby power systems shall be installed in
accordance with the International Building Code, NFPA 70, NFPA 110 and NFPA 111. Existing
installations shall be maintained in accordance with the original approval, except as specified in
Chapter 11.
604.1.3 through 604.1.8(No changes to these sections.
604.1.9 Critical Operations Power Systems (COPS). For Critical Operations Power Systems
necessary to maintain continuous power supply to facilities or parts of facilities that require continuous
eTh North Central Texas Council of Governments 9 As of August 2015 IFC Amendments
operation for the reasons of public safety, emergency management, national security, or business
continuity, see NFPA 70.
604.2 Where Required. Emergency and standby power systems shall be provided where required by
Sections 604.2.1 through 604:2,46 604.2.24 or elsewhere identified in this code or any other referenced
code.
604.2.1 through 604.2.3{No change.}
604.2.4 . Emergency Voice/alarm Communications Systems. Emergency
power shall be provided for emergency voice/alarm communications systems in the following
occupancies, or as specified elsewhere in this code, as required in Section 907.5.2.2.5. The system shall
be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72.
Covered and Open Malls, Section 907.2.20 and 914.2.3
Group A Occupancies, Sections 907.2.1 and 907.5.2.2.4.
Special Amusement Buildings, Section 907.2.12.3
High-rise Buildings, Section 907.2.13
Atriums, Section 907.2.14
Deep Underground Buildings, Section 907.2.19
604.2.5 through 604.2.11 {No change.)
604.2.12 Means of Egress Illumination. Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1. (90 minutes)
604.2.13 Membrane Structures. Emergency power shall be provided for exit signs in temporary tents
and membrane structures in accordance with Section 3103.12.6.1. (90 minutes) Standby power shall be
provided for auxiliary inflation systems in permanent membrane structures in accordance with Section
2702 of the International Building Code. (4 hours) Auxiliary inflation systems shall be provided in
temporary air-supported and air-inflated membrane structures in accordance with section 3103.10.4.
604.2.14{No change.}
604.2.15 Smoke Control Systems. Standby power shall be provided for smoke control systems in the
following occupancies, or as specified elsewhere in this code, as required in Section 909.11:
Covered Mall Building, International Building Code, Section 402.7
Atriums, International Building Code, Section 404.7
Underground Buildings, International Building Code, Section 405.8
Group 1-3, International Building Code, Section 408.4.2
Stages, International Building Code, Section 410.3.7.2
Special Amusement Buildings (as applicable to Group A's), International Building Code, Section
411.1
Smoke Protected Seating, Section 1029.6.2.1
604.2.17 Covered and Open Mall Buildings. Emergency power shall be provided in accordance with
Section 907.2.20 and 914.2.3.
604.2.18 Airport Traffic Control Towers. A standby power system shall be provided in airport traffic
control towers more than 65 ft. in height. Power shall be provided to the following equipment:
1. Pressurization equipment, mechanical equipment and lighting.
2. Elevator operating equipment.
3. Fire alarm and smoke detection systems.
604.2.19 Smokeproof Enclosures and Stair Pressurization Alternative. Standby power shall be
provided for smokeproof enclosures, stair pressurization alternative and associated automatic fire
detection systems as required by the International Building Code, Section 909.20.6.2.
604.2.20 Elevator Pressurization. Standby power shall be provided for elevator pressurization system
as required by the International Building Code, Section 909.21.5.
604.2.21 Elimination of Smoke Dampers in Shaft Penetrations. Standby power shall be provided
when eliminating the smoke dampers in ducts penetrating shafts in accordance with the International
Building Code, Section 717.5.3, exception 2.3.
604.2.22 Common Exhaust Systems for Clothes Dryers. Standby power shall be provided for
common exhaust systems for clothes dryers located in multistory structures in accordance with the
International Mechanical Code, Section 504.10, Item 7.
604.2.23 Hydrogen Cutoff Rooms. Standby power shall be provided for mechanical ventilation and gas
detection systems of Hydrogen Cutoff Rooms in accordance with the International Building Code, Section
421.8.
North Central Texas Council of Governments 10 As of August 2015 IFC Amendments
604.2.24 Means of Egress Illumination in Existing Buildings. Emergency power shall be provided for
means of egress illumination in accordance with Section 1104.5 when required by the fire code official.
(90 minutes in 1-2, 60 minutes elsewhere.)
rill 604.3 through 604.7 {No change.}
604.8 Energy Time Duration. Unless a time limit is specified by the fire code official, in this chapter or
elsewhere in this code, or in any other referenced code or standard, the emergency and standby power
system shall be supplied with enough fuel or energy storage capacity for not less than 2-hour full-demand
operation of the system.
Exception: Where the system is supplied with natural pas from a utility provider and is
approved.
(Reason: These provisions provide a list to complete and match that throughout the codes. The only
new items are the reference to COPS in NFPA 70, and the specified Energy time duration. Other
chan•es are a reference to a code •rovision that a/read exists.
***Section 609.2;change to read as follows:
609.2 Where Required. A Type I hood shall be installed at or above all commercial cooking appliances
and domestic cooking appliances used for commercial purposes that produce grease vapors, including
but not limited to cooking equipment used in fixed, mobile, or temporary concessions, such as trucks,
buses, trailers, pavilions,or any form of roofed enclosure, as required by the fire code official.
Exceptions:
1. Tents, as provided for in Chapter 31.
2. {No change to existing Exception.}
Additionally, fuel gas and power provided for such cooking appliances shall be interlocked with the
extinguishing system, as required by Section 904.12.2. Fuel pas containers and piping/hose shall be
properly maintained in good working order and in accordance with all applicable regulations.
(Reason: To require fire protection and prevention for mobile food trucks and other mobile commercial
riN cooking operations for the protection of occupants and first responders, including the fuel gas utilized for
the cookin• o•eration.
**Section 704.1;change to read as follows:
704.1 Enclosure. Interior vertical shafts including, but not limited to, stairways, elevator hoistways,
service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in
accordance with the codes in effect at the time of construction but, regardless of when constructed, not
less than as required in Chapter 11. New floor openings in existing buildings shall comply with the
International Building Code.
(Reason: Provides standard minimum protection retroactively, but clarifies that this section is not to be
used to reduce higher protection levels that were required when originally constructed.)
***Section 807.3;change to read as follows:
807.3 Combustible Decorative Materials. In occupancies in Groups A, E, I, and
R-1, and dormitories in Group R-2, curtains, draperies, fabric hangings and other similar combustible
decorative materials suspended from walls or ceilings shall comply with Section 807.4 and shall not
exceed 10 percent of the specific wall or ceiling area to which they are attached.
(Reason: Section 807 was re-arranged and modified from the 2012 IFC: previously, curtains were
required to be NFPA 701 compliant and limited to 10 percent of the applicable wall in A, E, I, R-1, and R-2
dormitory occupancies, but now, per the published 2015 1FC, Section 807.3 would apply to all
occupancies, except 1-3(non-combustible only). Such a change is a tremendous expansion of the
requirement, and no justification was provided in the proposed code change at the code hearings as to
the reasons for such an expansion of the requirement, especially considering that it also applies to
North Central Texas Council of Governments 11 As of August 2015 IFC Amendments
existing buildings. The board believes that this change is an over-reach for such a stringent requirement
and that maintenance of the legacy Ian•uage is ap•ropriate at this time.)
**Section 807.5.2.2 and 807.5.2.3;change to read as follows:
807.5.2.2 Artwork in Corridors.Artwork and teaching materials shall be limited on the walls of corridors
to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling
or wall to wall. Curtains, draperies, wall hangings, and other decorative material suspended from the
walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with
Section 807 or be noncombustible.
Exception: Corridors protected by an approved automatic sprinkler system installed in accordance
with Section 903.3.1.1 shall be limited to 50 percent of the wall area.
807.5.2.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of
classrooms to not more than 50 percent of the specific wall area to which they are attached.
Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings
shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be
noncombustible.
(Reason: This change allows an increase in wall coverage due to the presence of sprinklers. Also
•rovides additional •uidance relative to fire resistance re•uirements in these areas.
**Section 807.5.5.2 and 807.5.5.3;change to read as follows:
807.5.5.2 Artwork in Corridors. Artwork and teaching materials shall be limited on the walls of corridors
to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling
or wall to wall. Curtains, draperies, wall hangings and other decorative material suspended from the walls
or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section
807 or be noncombustible.
Exception: Corridors protected by an approved automatic sprinkler system installed in accordance
,ram with Section 903.3.1.1 shall be limited to 50 percent of the wall area.
807.5.5.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of
classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains.
draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet
the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be
noncombustible.
(Reason: This change allows an increase in wall coverage due to the presence of sprinklers. Also
provides additional guidance relative to fire resistance requirements in these areas.)
**Section 901.6.1;add Section 901.6.1.1 to read as follows:
901.6.1.1 Standpipe Testing. Building owners/managers must maintain and test standpipe systems as
per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is
required every 5 years:
1. The piping between the Fire Department Connection (FDC) and the standpipe shall be backflushed
when foreign material is present, and also hydrostatically tested for all FDC's on any type of
standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25
requirements for the different types of standpipe systems.
2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of
flowing water through the standpipe, the tester shall connect hose from a fire hydrant or portable
pumping system (as approved by the fire code official) to each FDC, and flow water through the
standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm
that there are no open hose valves prior to introducing water into a dry standpipe. There is no
l North Central Texas Council of Governments 12 As of August 2015 IFC Amendments
required pressure criteria at the outlet. Verify that check valves function properly and that there are
no closed control valves on the system.
(NI 3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements
of NFPA 25.All hose valves shall be exercised.
4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all
FDC's as required by the fire code official.
5. Upon successful completion of standpipe test, place a blue tag (as per Texas Administrative Code,
Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the bottom of
each standpipe riser in the building. The tag shall be check-marked as"Fifth Year"for Type of ITM,
and the note on the back of the tag shall read"5 Year Standpipe Test'at a minimum.
6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to Yellow
Tags and Red Tags or any deficiencies noted during the testing, including the required
notification of the local Authority Having Jurisdiction (fire code official)shall be followed.
7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable,
as required by the State Rules mentioned above and NFPA 25.
8. Standpipe system tests where water will be flowed external to the building shall not be conducted
during freezing conditions or during the day prior to expected night time freezing conditions.
9. Contact the fire code official for requests to remove existing fire hose from Class II and III standpipe
systems where employees are not trained in the utilization of this firefighting equipment. All
standpipe hose valves must remain in place and be provided with an approved cap and chain when
approval is given to remove hose by the fire code official.
(Reason: Increases the reliability of the fire protection system and re-emphasizes the requirements of
1, NFPA 25 relative to standpipe systems, as well as ensuring that FDC connections are similarly
tested/maintained to ensure o•eration in an eme •enc incident.
"Section 901.6.3;add Section 901.6.3 to read as follows:
901.6.3 False Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given,
signaled or transmitted or caused or permitted to be given, signaled or transmitted in any manner.
(Reason: Places the responsibility on the business or property owner to maintain their fire alarm systems
in approved condition. Allows the enforcement of`prohibition of false alarms". Replaces text lost from the
le•ac codes that hel.s to ensure the maintenance of life safet s stems.
"Section 901.7;change to read as follows:
901.7 Systems Out of Service. Where a required fire protection system is out of service or in the event
of an excessive number of activations, the fire department and the fire code official shall be notified
immediately and, where required by the fire code official, the building shall either be evacuated or an
approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire
protection system has been returned to service. ... (remaining text unchanged)
(Reason: Gives fire code official more discretion with regards to enforcement of facilities experiencing
nuisance alarm or fire protection system activations necessitating correction/repair/replacement. The
intent of the amendment is to allow local jurisdictions to enforce fire watches, etc., where needed to
ensure safety of occupants where fire protection systems are experiencing multiple nuisance activations.
telS North Central Texas Council of Governments 13 As of August 2015 IFC Amendments
***Section 901.8.2;change to read as follows:
901.8.2 Removal of existing Occupant-use Hose Lines. The fire code official is authorized to permit
the removal of existing occupant-use hose lines and hose valves where all of the following conditions
exist:
1.
2. The hose lined would not be utilized by trained personnel or the fire department.
3. T-If the remaining--outlets occupant-use hose lines are removed, but the hose valves are
required to remain as per the fire code official, such shall be ace compatible with local fire
department fittings.
(Reason: Occupant-use hose lines have been an issue of concern that fire code officials have struggled
with for many years now, primarily in that they are required by the published code, even though
occupants are rarely property trained in their use or provided with the OSHA-required protective gear for
such use, such as with an industrial fire brigade. The allowance for these hose lines to remain only
promotes the possibility of an occupant attempting to fight fire for an unknown duration, rather than
evacuate, and potentially injure themselves or others through such action. They present greater risk than
benefit to the occupants, and as such, the above gives the fire code official the authorization to allow
removal of such at his or her discretion.)
**Section 903.1.1;change to read as follows:
903.1.1 Alternative Protection. Alternative automatic fire-extinguishing systems complying with Section
904 shall be permitted instead of in addition to automatic sprinkler protection where recognized by the
applicable standard and or as approved by the fire code official.
(Reason: Such alternative systems do not provide the reliability of automatic sprinkler protection. Most
, +� gaseous type systems are highly susceptible to open doors, ceiling or floor tile removal, etc. However, an
nI' applicant could pursue an Alternate Method request to help mitigate the reliability issues with these
alternative systems with the fire code official if so desired, or there may be circumstances in which the fire
code official is acceptable to allowing an alternate system in lieu of sprinklers, such as kitchen hoods or
•aint booths.
**Section 903.2;add paragraph to read as follows:
Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and
elevator hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements
under any circumstances. Storage shall not be allowed within the elevator machine room. Signage shall
be provided at the entry doors to the elevator machine room indicating "ELEVATOR MACHINERY— NO
STORAGE ALLOWED."
(Reason: Firefighter and public safety. This amendment eliminates the shunt trip requirement of the
International Building Code Section 3006.5 for the purpose of elevator passenger and firefighter safety.
This amendment is contingent on the Building Code amendment eliminating the Exceptions to Section
3006.4, such that •assive fire barriers for these areas are maintained.
**Section 903.2;delete the exception.
(Reason: The exception deletion is due to the fact that such telecom areas pose an undue fire risk to the
structural integrity of the building.)
n North Central Texas Council of Governments 14 As of August 2015 IFC Amendments
***Section 903.2.9;add Section 903.2.9.3 to read as follows:
903.2.9.3 Self-Service Storage Facility. An automatic sprinkler system shall be installed throughout all
self-service storage facilities.
(Reason: Fire departments are unable to inspect these commercial occupancies and are unaware of the
contents being stored. Previous allowance to separate units by fire barriers is difficult to enforce
maintenance after opening.)
**Option A
Section 903.2.11;change 903.2.11.3 and add 903.2.11.7 and 903.2.11.8,as follows:
903.2.11.3 Buildings 55 Feet or more in Height. An automatic sprinkler system shall be installed
throughout buildings that have one or more stories , other than
penthouses in compliance with Section 1510 of the International Building Code, located 55 feet(16
764 mm) or more above the lowest level of fire department vehicle access, measured to the finished
floor.
Exceptions:
1—Open parking structures in compliance with Section 406.5 of the International Building
Code, having no other occupancies above the subject garage.
903.2.11.7 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet
(4572 mm), see Chapter 32 to determine if those provisions apply.
903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be
protected by an approved automatic fire-extinguishing system.
North Central Texas Council of Governments 15 As of August 2015 IFC Amendments
**Option B
eTh Section 903.2.11;change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows:
903.2.11.3 Buildings 66 35 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings that have one or more stories , other than
penthouses in compliance with Section 1510 of the International Building Code, located 55 35 feet
(16 761 10 668 mm) or more above the lowest level of fire department vehicle access, measured to
the finished floor.
Exceptions:
4—Open parking structures in compliance with Section 406.5 of the International Building
Code, having no other occupancies above the subject garage.
903.2.11.7 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet
(4572 mm), see Chapter 32 to determine if those provisions apply.
903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be
protected by an approved automatic fire-extinguishing system.
903.2.11.9 Buildings Over 6.000 sq. .ft. An automatic sprinkler system shall be installed throughout
all buildings with a building area 6,000 sq. ft. or greater and in all existing buildings that are enlarged
to be 6,000 sa. ft. or greater. For the purpose of this provision, fire walls shall not define separate
buildings.
Exception: Open parking garages in compliance with Section 406.5 of the International Building
Code.
ems
(Reason: Provides jurisdictions options as to their desired level of sprinkler protection based on multiple
factors includin• firefighting philosophies/capabilities.
**Section 903.3.1.1.1;change to read as follows:
903.3.1.1.1 Exempt Locations. When approved by the fire code official, automatic sprinklers shall not
be required in the following rooms or areas where such ...(text unchanged)... because it is damp, of fire-
resistance-rated construction or contains electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or fire
hazard.
2. Any room or space where sprinklers are considered undesirable because of the nature of the
contents,when approved by the code official.
3. Generator and transformer rooms, under the direct control of a public utility. separated from the
remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-
resistance rating of not less than 2 hours.
5. Elevator machine rooms, and machinery spaces, and hoistways, other than
pits where such sprinklers would not necessitate shunt trip requirements under any
circumstances.
6. {Delete.}
(Reason: Gives more direction to code official. Exception 4 deleted to provide protection where fire risks
are poorly addressed. Amendment 903.2 addresses Exception 5 above relative to the elimination of
sprinkler protection in these areas to avoid the shunt trip requirement.)
North Central Texas Council of Governments 16 As of August 2015 IFC Amendments
**Section 903.3.1.2.3;add section to read as follows:
""IS [F] Section 903.3.1.2.3 Attics and Attached Garages. Sprinkler protection is required in attic spaces of
such buildings two or more stories in height, in accordance with NFPA 13 and or NFPA 13R
requirements, and attached garages.
(Reason:Attic protection is required due to issues with fire exposure via soffit vents, as well as firefighter
safety. Several jurisdictions indicated experience with un-protected attic fires resulting in displacement of
all building occupants. NFPA 13 provides for applicable attic sprinkler protection requirements, as well as
exemptions to such, based on noncombustible construction, etc. Attached garages already require
sprinklers via NFPA 13R—this amendment just re-emphasizes the requirement.)
***Section 903.3.1.3;change to read as follows:
903.3.1.3 NFPA 13D Sprinkler Systems. Automatic sprinkler systems installed in one- and two-family
dwellings; Group R-3; Group R-4 Condition 1 and townhouses shall be permitted to be installed
throughout in accordance with NFPA 13D or in accordance with state law.
(Reason: To allow the use of the Plumbing section of the International Residential Code (IRC) and
reco•nize current state sti.ulations in this re•ard.
***Section 903.3.1.4;add to read as follows:
[F]903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be
in accordance with the requirements of the applicable referenced NFPA standard and this section.
903.3.1.4.1 Attics. Only dry-pipe, preaction, or listed antifreeze automatic fire sprinkler systems
shall be allowed to protect attic spaces.
Exception: Wet-pipe fire sprinkler systems shall be allowed to protect non-ventilated attic
spaces where:
rts 1. The attic sprinklers are supplied by a separate floor control valve assembly to
allow ease of draining the attic system without impairing sprinklers throughout the
rest of the building, and
2. Adequate heat shall be provided for freeze protection as per the applicable
referenced NFPA standard, and
3. The attic space is a part of the building's thermal, or heat, envelope, such that
insulation is provided at the roof deck, rather than at the ceiling level.
903.3.1.4.2 Heat trace/insulation. Heat trace/insulation shall only be allowed where approved by
the fire code official for small sections of large diameter water-filled pipe.
(Reason: In the last few years, severe winters brought to light several issues with current practices for
sprinklering attics, not the least of which was wet-pipe sprinklers in ventilated attics provided with space
heaters, etc. for freeze protection of such piping. This practice is not acceptable for the protection of
water-filled piping in a ventilated attic space as it does not provide a reliable means of maintaining the
minimum 40 degrees required by NFPA, wastes energy, and presents a potential ignition source to the
attic space. Listed antifreeze is specifically included because NFPA currently allows such even though
there is no currently listed antifreeze at the time of development of these amendments. The intent of this
amendment is to help reduce the large number of freeze breaks that have occurred in the past with water-
filled wet-pi.e sprinkler systems in the future, most specifically in attic spaces.)
**Section 903.3.5;add a second paragraph to read as follows:
[F] Water supply as required for such systems shall be provided in conformance with the supply
requirements of the respective standards; however every water-based fire protection system shall be
designed with a 10 psi safety factor. Reference Section 507.4 for additional design requirements.
(Reason: To define uniform safety factor.)
nNorth Central Texas Council of Governments 17 As of August 2015 IFC Amendments
**Section 903.4;add a second paragraph after the exceptions to read as follows:
eeNt Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler
system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control
valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be
electrically supervised to initiate a supervisory signal at the central station upon tampering.
(Reason: To avoid significant water losses. Consistent with amendment to IFC 905.9.)
**Section 903.4.2;add second paragraph to read as follows:
The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification
appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire
department connection.
(Reason: Fire department connections are not always located at the riser; this allows the fire department
faster access.)
**Section 905.2;change to read as follows:
905.2 Installation Standard. Standpipe systems shall be installed in accordance with this section and
NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psiq and a maximum
of 40 psig air pressure with a high/low alarm.
(Reason: To define manual dry standpipe supervision requirements. Helps ensure the integrity of the
stand•i•e s stem via su•ervision, such that o•en hose valves will result in a su•erviso low air alarm.
***Section 905.3;add Section 905.3.9 and exception to read as follows:
(Ns 905.3.9 Buildings Exceeding 10,000 sq.ft. In buildings exceeding 10,000 square feet in area per story
and where any portion of the building's interior area is more than 200 feet(60960 mm) of travel, vertically
and horizontally, from the nearest point of fire department vehicle access, Class I automatic wet or
manual wet standpipes shall be provided.
Exceptions:
1. Automatic dry and semi-automatic dry standpipes are allowed as provided for in NFPA 14.
2. R-2 occupancies of four stories or less in height having no interior corridors.
(Reason:Allows for the rapid deployment of hose lines to the body of the fire.)
***Section 905.4, change Item 1, 3, and 5, and add Item 7 to read as follows:
1. In every required interior exit stairway, a hose connection shall be provided for each story above
and below grade plane. Hose connections shall be located at an intermediate landing between
stories, unless otherwise approved by the fire code official.
2. {No change.)
3. In every exit passageway, at the entrance from the exit passageway to other areas of a building.
Exception: Where floor areas adjacent to an exit passageway are reachable from an interior exit
stairway hose connection by a {No change to rest.)
4. {No change.}
5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope),
each standpipe shall be provided with a two-way a-hose connection shall-be located to serve the
roof or at the highest landing of an interior exit stairway with stair access to the roof provided in
accordance with Section 1011.12.
6. {No change.)
(Ns North Central Texas Council of Governments 18 As of August 2015 IFC Amendments
7. When required by this Chapter, standpipe connections shall be placed adjacent to all required
exits to the structure and at two hundred feet(200') intervals along major corridors thereafter, or as
otherwise approved by the fire code official.
friNt
(Reason: Item 1, 3, and 5 amendments to remove `interior' will help to clarify that such connections are
required for all `exit'stairways, to ensure firefighter capabilities are not diminished in these tall buildings,
simply because the stair is on the exterior of the building. Item 5 reduces the amount of pressure required
to facilitate testing, and provides backup protection for fire fighter safety. Item 7 allows for the rapid
deployment of hose lines to the body of the fire.)
**Section 905.9;add a second paragraph after the exceptions to read as follows:
Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler
system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control
valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be
electrically supervised to initiate a supervisory signal at the central station upon tampering.
(Reason: To avoid significant water losses. Consistent with amendment to IFC 903.4.)
**Section 907.1;add Section 907.1.4 and 907.1.4.1 to read as follows:
907.1.4 Design Standards. Where a new fire alarm system is installed, the devices shall be
addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog initiating
devices.
(Reason: Provides for the ability of descriptive identification of alarms, and reduces need for panel
replacement in the future. Updated wording to match the language of the new requirement at 907.5.2.3.
Change of terminology allows for reference back to definitions of NFPA 72)
( **Section 907.2.1;change to read as follows:
907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in
accordance with Section 907.5 shall be installed in Group A occupancies where--the having an occupant
load of 300 or more persons or more than 100 persons above or below
the lowest level of exit discharge. Group A occupancies not separated from one another in accordance
with Section 707.3.-10 of the International Building Code shall be considered as a single occupancy for
the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes
shall be provided with a fire alarm system as required for the Group E occupancy.
Exception: {No change.}
Activation of fire alarm notification appliances shall:
1. Cause illumination of the means of egress with light of not less than 1 foot-candle (11 lux) at the
walking surface level, and
2. Stop any conflicting or confusing sounds and visual distractions.
(Reason: Increases the requirement to be consistent with Group B requirement. Also addresses issue
found in Group A occupancies of reduced lighting levels and other AN equipment that distracts from fire
alarm notification devices or reduces ability of fire alarm system to notify occupants of the emergency
condition.
***Section 907.2.3;change to read as follows:
907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an
emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and
installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When
automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be
North Central Texas Council of Governments 19 As of August 2015 IFC Amendments
connected to the building fire alarm system. An approved smoke detection system shall be installed in
Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings,
whether portable buildings or the main building, will be considered one building for alarm occupant load
rot consideration and interconnection of alarm systems.
Exceptions:
1. {No change.}
1.1.Residential In-Home day care with not more than 12 children may use interconnected
single station detectors in all habitable rooms. (For care of more than five children 2 1/2
or less years of age, see Section 907.2.6.) {No change to remainder of exceptions.}
(Reason: To distinguish educational from day care occupancy minimum protection requirements. Further,
to define threshold at which portable buildings are considered a separate building for the purposes of
alarm systems. Exceptions provide consistency with State law concerning such occupancies.)
**Section 907.2.13,Exception 3;change to read as follows:
3. Open air portions of buildings with an occupancy in Group A-5 in accordance with Section 303.1 of
the International Building Code; however, this exception does not apply to accessory uses including
but not limited to sky boxes, restaurants, and similarly enclosed areas.
(Reason: To indicate that enclosed areas within open air seating type occupancies are not exempted
from automatic fire alarm s stem re•uirements.
**Section 907.4.2;add Section 907.4.2.7 to read as follows:
907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type.
(Reason:Helps to reduce false alarms.)
ris ***Section 907.6.1;add Section 907.6.1.1 to read as follows:
907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a manner that a failure of
any single initiating device or single open in an initiating circuit conductor will not interfere with the normal
operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a
single open will not interfere with the operation of any addressable devices (Class A). Outgoing and
return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits
and shall have a minimum of four feet separation horizontal and one foot vertical between supply and
return circuit conductors. The initiating device circuit (IDC) from a signaling line circuit interface device
may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or
less.
(Reason: To provide uniformity in system specifications and guidance to design engineers. Improves
reliability of fire alarm devices and systems.)
**.*Section 907.6.3;delete all four Exceptions.
(Reason: To assist responding personnel in locating the emergency event for all fire alarm systems. This
is moved from 907.6.5.3 in the 2012 IFC and reworded to match new code language and sections.)
***Section 907.6.6;—add sentence at end of paragraph to read as follows:
[F] See 907.6.3 for the required information transmitted to the supervising station.
(Reason: To assist responding personnel in locating the emergency event for all fire alarm systems. This
is moved from 907.6.5.3 in the 2012 IFC and reworded to match new code language and sections.)
I' 1 North Central Texas Council of Governments 20 As of August 2015 IFC Amendments
***Section 909.22;add to read as follows:
titS 909.22 Stairway or Ramp Pressurization Alternative. Where the building is equipped throughout with
an automatic sprinkler system in accordance with Section 903.3.1.1 and the stair pressurization
alternative is chosen for compliance with Building Code requirements for a smokeproof enclosure, interior
exit stairways or ramps shall be pressurized to a minimum of 0.10 inches of water (25 Pa) and a
maximum of 0.35 inches of water(87 Pa) in the shaft relative to the building measured with all interior exit
stairway and ramp doors closed under maximum anticipated conditions of stack effect and wind effect.
Such systems shall comply with Section 909, including the installation of a separate fire-fighter's smoke
control panel as per Section 909.16, and a Smoke Control Permit shall be required from the fire
department as per Section 105.7.
[F] 909.22.1 Ventilating equipment. The activation of ventilating equipment for the stair or ramp
pressurization system shall be by smoke detectors installed at each floor level at an approved location at
the entrance to the smokeproof enclosure. When the closing device for the stairway or ramp shaft and
vestibule doors is activated by smoke detection or power failure, the mechanical equipment shall activate
and operate at the required performance levels. Smoke detectors shall be installed in accordance with
Section 907.3.
909.22.1.1 Ventilation Systems. Smokeproof enclosure ventilation systems shall be independent of
other building ventilation systems. The equipment, control wiring, power wiring and ductwork shall comply
with one of the following:
1. Equipment, control wiring, power wiring and ductwork shall be located exterior to the building
and directly connected to the smokeproof enclosure or connected to the smokeproof
enclosure by ductwork enclosed by not less than 2-hour fire barriers constructed in
accordance with Section 707 of the Building Code or horizontal assemblies constructed in
accordance with Section 711 of the Building Code, or both.
2. Equipment, control wiring, power wiring and ductwork shall be located within the smokeproof
enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed
by not less than 2-hour barriers constructed in accordance with Section 707 of the Building
Code or horizontal assemblies constructed in accordance with Section 711 of the Building
Code, or both.
3. Equipment, control wiring, power wiring and ductwork shall be located within the building if
separated from the remainder of the building, including other mechanical equipment, by not
less than 2-hour fire barriers constructed in accordance with Section 707 of the Building Code
or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or
both.
Exceptions:
1. Control wiring and power wiring utilizing a 2-hour rated cable or cable system.
2.Where encased with not less than 2 inches(51 mm)of concrete.
3. Control wiring and power wiring protected by a listed electrical circuit protective systems with a
fire-resistance rating of not less than 2 hours.
909.21.1.2 Standby Power. Mechanical vestibule and stairway and ramp shaft ventilation systems and
automatic fire detection systems shall be provided with standby power in accordance with Section 2702 of
the Building Code.
909.22.1.3 Acceptance and Testing. Before the mechanical equipment is approved, the system shall be
tested in the presence of the fire code official to confirm that the system is operating in compliance with
these requirements.
(Reason: To assist with enforcement of such as a smoke control system, as per Section 909.6.3,
especially since a permit is now specifically required for such systems in the Fire Code. Also ensures that
a firefighter's override panel is provided as per 909.16 for such systems. The above amendment copies
the applicable requirements for such systems from Section 909.20 of the Building Code into the Fire
eTh North Central Texas Council of Governments 21 As of August 2015 IFC Amendments
Code. Although the published code did copy the elevator pressurization requirements into the Fire Code,
it did not co.),over the stair pressurization requirements.
***Section 910.2;change Exception 2.and 3.to read as follows:
[F] 2. Only manual smoke and heat removal shall net be required in areas of buildings equipped with
early suppression fast-response(ESFR) sprinklers.Automatic smoke and heat removal is
prohibited.
3. Only manual smoke and heat removal shall not be required in areas of buildings equipped with
control mode special application sprinklers with a response time index of 50(m*S)1f2 or less that
are listed to control a fire in stored commodities with 12 or fewer sprinklers. Automatic smoke
and heat removal is prohibited.
(Reason:Allows the fire department to control the smoke and heat during and after a fire event, while still
prohibiting such systems from being automatically activated, which is a potential detriment to the
particular sprinkler systems indicated.)
**Section 910.2;add subsections 910.2.3 with exceptions to read as follows:
910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows:
1. In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet
(1394 m2) in single floor area.
Exception: Buildings of noncombustible construction containing only noncombustible materials.
2. In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers,
Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive)
materials, or Class 2 or 3 water-reactive materials as required for a high-hazard commodity
classification.
Exception: Buildings of noncombustible construction containing only noncombustible materials.
(Reason: Maintains a fire protection device utilized in such occupancies where it is sometimes necessary
to allow chemicals to bum out, rather than extin•uish.
***Section 910.3;add section 910.3.4 to read as follows:
910.3.4 Vent Operation. Smoke and heat vents shall be capable of being operated by approved
automatic and manual means. Automatic operation of smoke and heat vents shall conform to the
provisions of Sections 910.3.2.1 through 910.3.2.3.
[F]910.3.4.1 Sprinklered buildings.Where installed in buildings equipped with an approved automatic
sprinkler system, smoke and heat vents shall be designed to operate automatically.
The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at
least 100 degrees F (approximately 38 degrees Celsius) greater than the temperature rating of the
sprinklers installed.
Exception: Manual only systems per Section 910.2.
910.3.4.2 Nonsprinklered Buildings. Where installed in buildings not equipped with an approved
automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-
responsive device rated at between 100°F(56°C)and 220°F (122°C)above ambient.
Exception: Listed gravity-operated drop out vents.
(Reason: Amendment continues to keep applicable wording from prior to the 2012 edition of the IFC.
Specifically, automatic activation criteria is no longer specifically required in the published code.
North Central Texas Council of Governments 22 As of August 2015 IFC Amendments
Specifying a temperature range at which smoke and heat vents should activate in sprinklered buildings
helps to ensure that the sprinkler system has an opportunity to activate and control the fire prior to vent
operation.)
***Section 910.4.3.1;change to read as follows:
910.4.3.1 Makeup Air. Makeup air openings shall be provided within 6 feet(1829 mm) of the floor level.
Operation of makeup air openings shall be manual-Of automatic. The minimum gross area of makeup air
inlets shall be 8 square feet per 1,000 cubic feet per minute(0.74 m2 per 0.4719 m3/s)of smoke exhaust.
(Reason: Makeup air has been required to be automatic for several years now in this region when
mechanical smoke exhaust systems are proposed. This allows such systems to be activated from the
smoke control panel by first responders without having to physically go around the exterior of the building
opening doors manually. Such requires a significant number of first responders on scene to conduct this
operation and significantly delays activation and/or capability of the smoke exhaust system.)
***Section 910.4.4;change to read as follows:
910.4.4 Activation. The mechanical smoke removal system shall be activated
automatically by the automatic sprinkler system or by an approved fire detection system. Individual
manual controls shall also be provided.
Exception: Manual only systems per Section 910.2.
(Reason: The provision of a manual only mechanical smoke removal system does not provide
equivalency with automatic smoke and heat vents. This amendment clarifies that the primary intent is for
automatic systems, unless exceptions are provided as in 910.2—consistent with the charging statements
of the section.)
**Section 912.2;add Section 912.2.3 to read as follows:
912.2.3 Hydrant Distance. An approved fire hydrant shall be located within 100 feet of the fire
department connection as the fire hose lays along an unobstructed path.
(Reason: To accommodate limited hose lengths, improve response times where the FDC is needed to
achieve fire control, and improve ease of locating a fire hydrant in those situations also. Also, consistent
with NFPA 14 criteria.)
**Section 913.2.1;add second paragraph and exception to read as follows:
When located on the ground level at an exterior wall, the fire pump room shall be provided with an
exterior fire department access door that is not less than 3 ft. in width and 6 ft. —8 in. in height, regardless
of any interior doors that are provided. A key box shall be provided at this door, as required by Section
506.1.
Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior
wall, the corridor leading to the fire pump room access from the exterior of the building shall be
provided with equivalent fire resistance as that required for the pump room, or as approved by the fire
code official. Access keys shall be provided in the key box as required by Section 506.1.
(Reason: This requirement allows fire fighters safer access to the fire pump room. The requirement
allows access without being required to enter the building and locate the fire pump room interior access
door during a fire event. The exception recognizes that this will not always be a feasible design scenario
for some buildings, and as such, provides an acceptable alternative to protect the pathway to the fire
pump room.)
l North Central Texas Council of Governments 23 As of August 2015 IFC Amendments
***Section 914.3.1.2;change to read as follows:
is 914.3.1.2 Water Supply to required Fire Pumps. In buildings that are more than 420 120 feet(128 m) in
building height, required fire pumps shall be supplied by connections to no fewer than two water mains
located in different streets. Separate supply piping shall be provided between each connection to the
water main and the pumps. Each connection and the supply piping between the connection and the
pumps shall be sized to supply the flow and pressure required for the pumps to operate.
Exception: {No change to exception.}
(Reason: The 2009 edition of the IFC added this requirement based on a need for redundancy of the
water supply similar to the redundancy of the power supply to the fire pumps required for such tall
buildings, partially due to the fact that these buildings are rarely fully evacuated in a fire event. More
commonly, the alarm activates on the floor of the event, the floor above and the floor below. Back-up
power to the fire pump becomes critical for this reason. Certainly, the power is pointless if the water
supply is impaired for any reason, so a similar requirement is provided here for redundant water supplies.
The 2015 edition changes the requirement to only apply to very tall buildings over 420 ft. This
amendment modifies/lowers the requirement to 120 ft., based on this same height requirement for fire
service access elevators. Again, the language from the 2009 and 2012 editions of the code applied to
any high-rise building. This compromise at 120 ft. is based on the above technical justification of defend-
in-place scenarios in fire incidents in such tall structures.)
**Section 1006.2.2.6; add a new Section 1006.2.2.6 as follows:
1006.2.2.6 Electrical Rooms. For electrical rooms, special exiting requirements may apply. Reference
the Electrical Code as adopted.
(Reason: Cross reference necessary for coordination with the NEC which has exiting requirements as
well.)
**Section 1009.1;add the following Exception 4:
Exceptions:
(previous exceptions unchanged)
4. Buildings regulated under State Law and built in accordance with State registered plans, including
any variances or waivers granted by the State, shall be deemed to be in compliance with the
requirements of Section 1009.
(Reason: To accommodate buildings regulated under Texas State Law and to be consistent with
amendments to Cha•ter 11.
**Section 1010.1.9.4 Bolt Locks;change Exceptions 3 and 4 to read as follows:
Exceptions:
3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S
occupancy. {Remainder unchanged}
4. Where a pair of doors serves a Group A, B, F, M or S occupancy{Remainder unchanged}
(Reason:Application to M occupancies reflects regional practice;No. 4 expanded to Group A due to it
being a similar scenario to other uses;No. 4 was regional practice.)
eriNi North Central Texas Council of Governments 24 As of August 2015 IFC Amendments
"**Section 1015.8 Window Openings;change number 1 to read as follows:
r ► 1. Operable windows where the top of the sill of the opening is located more than )
55 (16 764 mm) above the finished grade or other surface below and that are provided with window
fall prevention devices that comply with ASTM F 2006.
(Reason:In O•tion B 'urisdictions, change "75 feet"to "55 feet".
**Section 1020.1 Construction;add Exception 6 to read as follows:
6. In group B occupancies, corridor walls and ceilings need not be of fire-resistive construction within a
single tenant space when the space is equipped with approved automatic smoke-detection within the
corridor. The actuation of any detector shall activate self-annunciating alarms audible in all areas within
the corridor. Smoke detectors shall be connected to an approved automatic fire alarm system where such
system is provided.
(Reason: Revise the 2012 published NCTCOG amendment to this section to clarify intent is not to require
automatic fire alarm s stem or notification throu•bout the tenant s•ace, but rather, onl in the corridor.
**Section 1029.1.1.1; delete this section.Spaces under Grandstands and Bleachers:
(Reason: Unenforceable.)
**Section 1031.2;change to read as follows:
1031.2 Reliability. Required exit accesses, exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other emergency when-the
An exit or exit passageway shall not be used for
any purpose that interferes with a means of egress.
r e (Reason: Maintain legacy levels of protection and long-standing regional practice, and provide firefighter
safet .
**Section 1103.3;add sentence to end of paragraph as follows:
Provide emergency signage as required by Section 607.3.
Reason: Coordinates requirements of•revious amendment.
**Section 1103.5;add Section 1103.5.1 to read as follows:
1103.5.1 Group A-2.
Spray Booths and Rooms. Existing spray booths and spray rooms shall
be protected by an approved automatic fire-extinguishing system in accordance with Section 2404.
(Reason: Consistent with amendment to IFC 2404, and long-standing regional requirement.
The •ublished 1103.5.1 re•uirin• s•rinklers retroactive! in A-2 occu•ancies was deleted b ICC Errata.
***Section 1103.7; add Section 1103.7.8 and 1103.7.8.1 to read as follows:
1103.7.8 Fire Alarm System Design Standards. Where an existing fire alarm system is upgraded or
replaced, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke and/or heat
detectors shall have analog initiating devices.
Exception: Existing systems need not comply unless the total building, or fire alarm system, remodel
or expansion exceeds 30% of the building. When cumulative building, or fire alarm system, remodel
n North Central Texas Council of Governments 25 As of August 2015 IFC Amendments
or expansion initiated after the date of original fire alarm panel installation exceeds 50% of the
building, or fire alarm system, the fire alarm system must comply within 18 months of permit
application.
Ofri
1103.7.8.1 Communication requirements. Refer to Section 907.6.6 for applicable requirements.
(Reason: To assist responding personnel in locating the emergency event and provide clarity as to
percenta•es of work that results in a requirement to upgrade the entire fire alarm s stem.)
**Section 2304.1;change to read as follows:
2304.1 Supervision of Dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be
shall-be in accordance with Section 2., 01.3.the following:
1. Conducted by a qualified attendant; and/or,
2. Shall be under the supervision of a qualified attendant; and/or
3. Shall be an unattended self-service facility in accordance with Section 2304.3.
At any time the qualified attendant of item Number 1 or 2 above is not present, such operations shall be
considered as an unattended self-service facility and shall also comply with Section 2304.3.
(Reason:Allows a facility to apply the attended and unattended requirements of the code when both are
potentially applicable.)
**Section 2401.2;delete this section.
(Reason: This section eliminates such booths from all compliance with Chapter 15 including, but not
limited to: size, ventilation, fire protection, construction, etc. If the product utilized is changed to a more
flammable substance, the lack of compliance with Chapter 15 could result in significant fire or deflagration
and subse•uent life safet hazard.
***Table 3206.2, footnote j;change text to read as follows:
j. Net-regal-Where storage areas are protected by either early suppression fast response (ESFR)
sprinkler systems or control mode special application sprinklers with a response time index of 50(m •s)
1/2 or less that are listed to control a fire in the stored commodities with 12 or fewer sprinklers, installed
in accordance with NFPA 13, manual smoke and heat vents or manually activated enqineered
mechanical smoke exhaust systems shall be required within these areas.
(Reason: Allows the fire department to control the smoke and heat during and after a fire event, while
ensuring proper operation of the sprinkler protection provided. Also, gives an alternative to smoke and
heat vents.)
**Section 3310.1;add sentence to end of paragraph to read as follows:
When fire apparatus access roads are required to be installed for any structure or development, they shall
be approved prior to the time at which construction has progressed beyond completion of the foundation
of any structure.
Reason:Reference re•uirement of Section 501.4.
**Section 5601.1.3;change to read as follows:
n North Central Texas Council of Governments 26 As of August 2015 IFC Amendments
5601.1.3 Fireworks. The possession, manufacture, storage, sale, handling, and use of fireworks are
prohibited.
Exceptions:
1. Only when approved for fireworks displays, storage, and handling of fireworks as allowed in
Section 5604 and 5608.
3_:2. The use of fireworks for approved fireworks displays as allowed in Section 5608.
... (Delete remainder of text.]
(Reason: Restricts fireworks to approved displays only, which is consistent with regional practice. Such is
intended to help protect property owners and individuals from unintentional fireworks fires within the
jurisdiction, as well as to help protect individuals from fireworks injuries. It is noted that there has been a
change in the State Law to allow possession of unopened fireworks in certain areas of the vehicle, and it
is hi.hl recommended that AHJ's familiarize themselves with the applicable State Laws in this regard.
"*Section 5703.6;add a sentence to read as follows:
5703.6 Piping Systems. Piping systems, and their component parts, for flammable and combustible
liquids shall be in accordance with Sections 5703.6.1 through 5703.6.11. An approved method of
secondary containment shall be provided for underground tank and piping systems.
(Reason: Increased protection in response to underground leak problems and remediation difficulty in
underground applications. Coordinates with TCEQ requirements.)
"*Section 5704.2.9.5;change Section 5704.2.9.5 and add Section 5704.2.9.5.3 to read as follows:
em 5704.2.9.5 Above-ground Tanks Inside of Buildings. Above-ground tanks inside of buildings shall
comply with Section 5704.2.9.5.1 and 5704.2.9.5.2 through 5704.2.9.5.3.
5704.2.9.5.1 {No change.)
5704.2.9.5.2{No change.)
5704.2.9.5.3 Combustible Liquid Storage Tanks Inside of Buildings. The maximum aggregate
allowable quantity limit shall be 3,000 gallons (11 356 Li of Class II or III combustible liquid for storage in
protected aboveground tanks complying with Section 5704.2.9.7 when all of the following conditions are
met:
1. The entire 3,000 gallon (11 356 L)quantity shall be stored in protected above-ground tanks;
2. The 3,000 gallon (11 356 L)capacity shall be permitted to be stored in a single tank or multiple
smaller tanks;
3. The tanks shall be located in a room protected by an automatic sprinkler system complying with
Section 903.3.1.1; and
4. Tanks shall be connected to fuel-burning equipment, including generators, utilizing an approved
closed piping system.
The quantity of combustible liquid stored in tanks complying with this section shall not be counted towards
the maximum allowable quantity set forth in Table 5003.1.1(1), and such tanks shall not be required to be
located in a control area. Such tanks shall not be located more than two stories below grade.
(Reason:Relocated from exception to 603.3.2.1 as published, as per reason statement for deletion in that
section.)
n North Central Texas Council of Governments 27 As of August 2015 IFC Amendments
le"'S "Section 5704.2.11.4;add a sentence to read as follows:
5704.2.11.4 Leak Prevention. Leak prevention for underground tanks shall comply with Sections
5704.2.11.4.1 and 5701.2.11.5.2 through 5704.2.11.4.3. An approved method of secondary containment
shall be provided for underground tank and piping systems.
(Reason: Increased protection in response to underground leak problems and remediation difficulty in
unde •round a••lications.
"Section 5704.2.11.4.2;change to read as follows:
5704.2.11.4.2 Leak Detection. Underground storage tank systems shalt be provided with an approved
method of leak detection from any component of the system that is designed and installed in accordance
with NFPA 30 and as specified in Section 5704.2.11.4.3.
Reason:Reference to IFC Section 5704.2.11.4.3 amendment.)
**Section 5704.2.11.4;add Section 5704.2.11.4.3 to read as follows:
5704.2.11.4.3 Observation Wells. Approved sampling tubes of a minimum 4 inches in diameter shall be
installed in the backfill material of each underground flammable or combustible liquid storage tank. The
tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and
shall be provided with suitable surface access caps. Each tank site shall provide a sampling tube at the
corners of the excavation with a minimum of 4 tubes. Sampling tubes shall be placed in the product line
excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards
the dispensers, a minimum of two are required.
(Reason:Provides an economical means of checking potential leaks at each tank site.)
"Section 6103.2.1;add Section 6103.2.1.8 to read as follows:
6103.2.1.8 Jewelry Repair. Dental Labs and Similar Occupancies. Where natural gas service is not
available, portable LP-Gas containers are allowed to be used to supply approved torch assemblies or
similar appliances. Such containers shall not exceed 20-pound (9.0 kg) water capacity. Aggregate
capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other
containers by a distance of not less than 20 feet.
(Reason: To provide a consistent and reasonable means of regulating the use of portable LP-Gas
containers in these situations. Reduces the hazard presented by portable containers when natural gas is
already available. Please note that current State Law does not allow for the enforcement of any rules
more stringent than that adopted by the State, so this amendment is only applicable as to the extent
allowed by that State Law.)
Section 6104.2, Exception;add an exception 2 to read as follows:
Exceptions:
1. (existing text unchanged)
2. Except as permitted in Sections 308 and 6104.3.2, LP-gas containers are not permitted in
residential areas.
(Reason: To provide a consistent and reasonable means of regulating the use LP-Gas containers.
n North Central Texas Council of Governments 28 As of August 2015 IFC Amendments
Reduces the hazard presented by such containers when natural gas is already available. References
regional amendment to IFC 6104.3.2. Please note that current State Law does not allow for the
enforcement of any rules more stringent than that adopted by the State, so this amendment is only
applicable as to the extent allowed by that State Law.)
**Section 6104.3;add Section 6104.3.2 to read as follows:
6104.3.2 Spas, Pool Heaters, and Other Listed Devices. Where natural gas service is not available, an
LP-gas container is allowed to be used to supply spa and pool heaters or other listed devices. Such
container shall not exceed 250-gallon water capacity per lot. See Table 6104.3 for location of containers.
Exception: Lots where LP-gas can be off-loaded wholly on the property where the tank is located
may install up to 500 gallon above ground or 1,000 gallon underground approved containers.
(Reason:Allows for an alternate fuel source. Dwelling density must be considered and possibly factored
into zoning restrictions. Reduces the hazard presented by over-sized LP-Gas containers. Please note
that current State Law does not allow for the enforcement of any rules more stringent than that adopted
b the State, so this amendment is only applicable as to the extent allowed b that State Law.)
***Section 6107.4 and 6109.13;change to read as follows:
6107.4 Protecting Containers from Vehicles. Where exposed to vehicular damage due to proximity to
alleys, driveways or parking areas, LP-gas containers, regulators and piping shall be protected in
accordance with NFPA-58-Section 312.
6109.13 Protection of Containers. LP-gas containers shall be stored within a suitable enclosure or
otherwise protected against tampering. Vehicle impact protection shall be provided as required by Section
6107.4.
" (Reason: NFPA 58 does not provide substantial physical protection [it allows raised sidewalks, fencing,
ditches, parking bumpers as `vehicle barrier protection] of the container(s) from vehicular impact as is
required and has been required historically, as per Section 312, i.e. bollard protection. Further, the
exception to Section 6109.13 would allow for portable containers in ventilated metal cabinets to not
require any physical protection whatsoever from vehicular impact, regardless of the location of the
containers. Please note that current State Law does not allow for the enforcement of any rules more
stringent than that adopted by the State, so this amendment is only applicable as to the extent allowed by
that State Law.)
***(Applicable to those jurisdictions adopting Appendix B)
Table B105.2;change footnote a. to read as follows:
a. The reduced fire-flow shall be not less than 1,000 1.500 gallons per minute.
(Reason: The minimum fire-flow of 1,500 gpm for other than one-and two-family dwellings has existed
since the 2000 edition of the IFC, as well as the Uniform Fire Code before that. Little to no technical
justification was provided for the proposed code change at the code hearings. The board believes that the
already-allowed 75 percent reduction in required fire-flow for the provision of sprinkler protection is
already a significant trade-off. The minimum 1,500 gpm is not believed to be overly stringent for the vast
majority of public water works systems in this region, especially since it has existed as the requirement for
so many years. Further, the continued progression of trading off more and more requirements in the
codes for the provision of sprinkler protection has made these systems extremely operation-critical to the
safety of the occupants and properties in question. In other words, should the sprinkler system fail for
any reason, the fire-flow requirements drastically increase from that anticipated with a sprinkler-controlled
fire scenario.
n North Central Texas Council of Governments 29 As of August 2015 IFC Amendments
END
t
IN
f North Central Texas Council of Governments 30 As of August 2015 IFC Amendments